2018-06-13 06:11:54ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NEC 600.6A(1) DISCONNECT REQUIRED WITHIN SIGHT OF
 SIGN. PLAN SHOWS DISCONNECT AND POWER SUPPLY BEHIND
 HOLLOW BLOCK WALL.
  
 2. TO MEET THE REQUIREMENTS OF NEC 600.6A(1) FOR THE
 DISCONNECTS A CONTRACTOR HOLDING AN EC OR ER LICENSE
 MUST PULL THE ELEC-SUB PERMIT AND PERFORM THE WORK.
 CONTRACTOR THAT HAS APPLIED FOR PERMIT ONLY CARRIES AN
 ES LICENSE AND IS BEYOND THEIR SCOPE OF WORK.
 F.S. 489.505 (#19) AND F.A.C. 61G6-7.001 SPECIALTY
 ELECTRICAL CONTRACTORS (#2 SIGN SPECIALTY CONTRACTOR)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved