| 2018-06-13 06:11:54 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NEC 600.6A(1) DISCONNECT REQUIRED WITHIN SIGHT OF |
| | SIGN. PLAN SHOWS DISCONNECT AND POWER SUPPLY BEHIND |
| | HOLLOW BLOCK WALL. |
| | |
| | 2. TO MEET THE REQUIREMENTS OF NEC 600.6A(1) FOR THE |
| | DISCONNECTS A CONTRACTOR HOLDING AN EC OR ER LICENSE |
| | MUST PULL THE ELEC-SUB PERMIT AND PERFORM THE WORK. |
| | CONTRACTOR THAT HAS APPLIED FOR PERMIT ONLY CARRIES AN |
| | ES LICENSE AND IS BEYOND THEIR SCOPE OF WORK. |
| | F.S. 489.505 (#19) AND F.A.C. 61G6-7.001 SPECIALTY |
| | ELECTRICAL CONTRACTORS (#2 SIGN SPECIALTY CONTRACTOR) |
| | |
| | END OF COMMENTS. |
| | |