| 2018-07-20 15:49:53 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18041063 & 18041175 (MAIN HOUSE AND |
| | GARAGE) |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1.OK |
| | |
| | 2.DRAINAGE PLAN PROVIDED NEEDS TO SHOW NUMERIC CHANGES |
| | IN ELEVATION THAT MEET REQUIRMENTS IN R401.3 |
| | [FBC 107.3.5.3]LOWEST FINISHED FLOOR ELEVATION NEEDS TO |
| | BE ESTABLISHED SINCE IT IS NOT ON SURVEY OR PLANS. |
| | PIPING FROM SCUPPERS IS NOT REQUIRED IF GRADE WILL |
| | PROVIDE PROPER DRAINAGE. IF PIPING IS USED WE NEED TO |
| | SEE HOW IT IS PITCHED AND HOW IT RELEASES TO THE |
| | STREET. |
| | 2-2. NO ELEVATIONS WERE PROVIDED. PLEASE ESTABLISH THE |
| | LOWEST FLOOR ELEVATION AND SUPPLY ELEVATIONS THAT WILL |
| | HELP US DETERMINE IF YOU ARE MEETING DRAINAGE |
| | REQUIREMENTS. THE EAST PROPERTY LINE, THE LOWEST FLOOR, |
| | THE TOP OF WALL, THE SIDEWALK AND THE STREET DRAIN |
| | WOULD BE A GOOD STARTING POINT. ALL ELEVATIONS SHOULD |
| | BE IN NAVD88. |
| | |
| | 3-09 OK |
| | |
| | 10.[ENERGY (RE402.1.2]THE ENERGY CALCS PROVIDED SHOW |
| | THE WALLS TO BE RATED AT R-14 WITH INT INSULATION. HOW |
| | WILL THIS R-RATING BE ACHIEVED AND PROVIDE THE |
| | DOCUMENTATION OF THE PRODUCT. ADJUST PLANS AND ENERGY |
| | CALCULATIONS TO MATCH. |
| | 10-2. THE INSULATION SPEC PROVIDED WOULD NOT BE ABLE TO |
| | ACHIEVE THE R-VALUE INDICATED IN THE ENERGY |
| | CALCULATIONS. PLEASE UPDATE THE ENERGY CALCULATIONS TO |
| | BE BASED ON WHAT WILL BE PROVIDED FOR WALL R-VALUE. |
| | |
| | 11-18 OK |
| | |
| | NOTE: |
| | ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF ADDITIONAL MATERIALS REQUESTED. |
| | |
| | |