2018-06-13 07:19:002ND GAS REVIEW**DENIED** WITH COMMENTS NOTE - A
 COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME AND
 ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED UPON
 THE RE-REVIEW OF SUBMITTED CORRECTIONS. SOME COMMENT
 MAY NOT APPLY BUT ARE PROVIDED FOR REFERENCES.
  
 1. WATER HEATER WILL REQUIRE A SEPARATE IGNITION SOURCE
 AND IT IS BEING LABELED ON AS A ELECTRICAL LOAD, PLEASE
 REMOVE AND ADD A SEPARATE CIRCUIT FOR IGNITION ON
 TANKLESS, WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 2. A SECOND REQUEST FOR FIREPLACE ON MANUFACTURES
 SPECIFICATION, FBC FG R2434.1 GENERAL.
 3. SHOW 2 PSI REGULATOR ON ISOMETRIC AND ALL REGULATORS
 DOWNSTREAM, SHOW THE LOCATION OF ALL MP (STEP-DOWN)
 REGULATORS. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR ON ISOMETRIC.
 2017 FBC FUEL GAS RES. SEC. G2420.4. SUBMIT
 MANUFACTURER?S SPECIFICATIONS FOR THE PRESSURE
 REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION.
 2017 FBC FUEL GAS RES. SEC. G2421.1.
 4. TYPE OF GAS (LP OR NATURAL) NEED TO BE LABELED ON
 ISOMETRIC. WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 5. SECOND REQUEST, PLEASE SUBMIT A DETAIL SHOWING THE
 TYPE, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 2017 FBC FUEL GAS SECS. 502 THRU 505 OR 2017 FBC FUEL
 GAS RES. SECS. G2426 THRU G2429.1
 6. SECOND REQUEST, PLEASE SUBMIT TWO COPIES OF THE
 APPLICABLE SIZING TABLES USED TO SIZE THE GAS SYSTEM OR
 PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH
 SIZING TABLE(S) FROM THE GAS CODE OR ANOTHER STANDARD
 THAT WAS USED IN THE DESIGN OF THIS GAS SYSTEM. REFER
 TO THE 2017 FBC FUEL GAS RES. SEC. G2412.4, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 7. SECOND REQUEST, SUBMIT COMBUSTION AIR CALCULATIONS
 FOR DRYER GAS APPLIANCES. WHERE IS COMBUSTION AIR
 PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION
 SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED
 COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED
 VENTILATION AIR? 2017 FBC R G2407.9.3. COMBINED
 COMBUSTION AIR AND VENTILATION AIR SYSTEM.
  
 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS NOTE - A
 COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME AND
 ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED UPON
 THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  