| 2018-06-22 12:52:49 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1.OK |
| | |
| | 2.DRAINAGE PLAN PROVIDED NEEDS TO SHOW NUMERIC CHANGES |
| | IN ELEVATION THAT MEET REQUIRMENTS IN R401.3 |
| | [FBC 107.3.5.3]LOWEST FINISHED FLOOR ELEVATION NEEDS TO |
| | BE ESTABLISHED SINCE IT IS NOT ON SURVEY OR PLANS. |
| | PIPING FROM SCUPPERS IS NOT REQUIRED IF GRADE WILL |
| | PROVIDE PROPER DRAINAGE. IF PIPING IS USED WE NEED TO |
| | SEE HOW IT IS PITCHED AND HOW IT RELEASES TO THE |
| | STREET. |
| | |
| | 3.THE REPORT PROVIDED IS GOOD, BUT PLEASE CHOOSE ONLY |
| | ONE TYPE OF ICYNENE. IT IS EITHER CLASSIC OR CLASSIC |
| | PLUS BECAUSE THEY REQUIRE DIFFERENT THICKNESS TO |
| | ACHIEVE R-30. |
| | |
| | NEW COMMENTS BELOW FROM FULL REVIEW: |
| | |
| | 4.[FBC R301]CHANGE ADDRESS ON SURVEY TO SAY 620 PARK |
| | PLACE ON BOTH SURVEY SHEETS. THE SURVEYOR PUT 618 ON |
| | THE SHEET SHOWING HOUSE LAYOUT. |
| | |
| | 5.[FBC R311.3.1]EGRESS LANDING SHALL NOT BE LESS THAN 1 |
| | 1/2" LOWER THAN THE TOP OF THRESHOLD. PROVIDE DIMENSION |
| | ON SECTION TO SHOW HOW YOU ARE MEETING CODE PROVISION. |
| | |
| | 6.[FBC 107.3.5.3]SHOW SECTION CUTS ON PLAN SHEET A-1 TO |
| | CORRESPOND TO SECTIONS ON SHEET A-6, ADD NORTH ARROW TO |
| | A-1, ADD ELEVATION CALLOUTS ON A-1 TO CORRESPOND TO |
| | ELEVATION SHEET A-2, ADD ROOF PITCH TO ELEVATIONS AND |
| | SECTIONS AND CONSIDER ADDING WINDOW DESIGNATIONS TO |
| | ELEVATION SHEET A-2 TO MATCH DESIGNATIONS ON PLAN SHEET |
| | A-1. |
| | |
| | 7.[FBC R318]INDICATE THE MEANS OF TERMITE PROTECTION |
| | PROPOSED AND REFERENCE SECTION R308 FOR STANDARDS. |
| | |
| | 8.[FBC R308.1]ADD NOTE FOR SHOWER ENCLOSURES TO COMPLY |
| | WITH SAFETY GLASS STANDARDS. |
| | |
| | 9.[FBC R403.1(3) ADD NOTE TO SECTIONS SHOWING |
| | REINFORCING TO PROVIDE MINIMUM COVER OF 3" FOR |
| | REINFORCING BARS. |
| | |
| | 10.[ENERGY (RE402.1.2]THE ENERGY CALCS PROVIDED SHOW |
| | THE WALLS TO BE RATED AT R-14 WITH INT INSULATION. HOW |
| | WILL THIS R-RATING BE ACHIEVED AND PROVIDE THE |
| | DOCUMENTATION OF THE PRODUCT. ADJUST PLANS AND ENERGY |
| | CALCULATIONS TO MATCH. |
| | |
| | NOTICE OF ACCEPTANCE (N.O.A.): |
| | |
| | 11.PRINT DRAWING SHEETS IN LANDSCAPE FORMAT TO FIT THE |
| | PAGE BETTER. SOME ARE LEDIBLE, BUT SOME PRESSURE CHARTS |
| | ARE TOO HARD TO READ. |
| | THIS APPLIES TO NOA 17-1023.09, 17-0630.08 AND |
| | 17-0614.14. |
| | |
| | 12.PROVIDE 2 COPIES OF N.O.A. FOR INTENDED MULL BAR TO |
| | BE USED IN BEDROOM, OFFICE, MASTER BATH AND VERIFY IF |
| | MULL IS BEING USED IN GARAGE 2ND FL WEST ELEVATION. THE |
| | ELEVATION SHOWS DIFFERENT THAN THE PLAN LOFT WEST ELEV. |
| | 2ND FL. WINDOWS. |
| | |
| | 13.HIGHLIGHT ANCHOR OPTION FOR APPLICABLE BUILDING |
| | SYSTEM BEING USED ON WINDOW AND DOOR N.O.A.'S. |
| | |
| | 14.N.O.A. 14-0506.02 IS MISSING PRESSURE DATA. PLEASE |
| | INSERT MISSING SHEET(S). ALSO, CHECK THAT THIS IS THE |
| | INTENDED DOOR TYPE FOR THE SINGLE DOORS. THE DOOR |
| | SCHEDULE CALLS OUT HOLLOW METAL DOORS BUT THE N.O.A IS |
| | FOR FIBERGLASS. UPDATE DOOR SCEDULE TO MATCH N.O.A. |
| | BEING USED. |
| | |
| | 15.SELECT WHICH TYPE OF UNDERLAYMENT IS TO BE INSTALLED |
| | PER N.O.A 15-0410.04. |
| | |
| | ROOFING COMMENTS: |
| | |
| | 16.[FBC R903.2.1] SUBMIT FLASHING TYPE, GAGE AND |
| | ATTACHMENT DETAILS. PROVIDE SCUPPER DETAIL, SIZE AND |
| | ROOF AREA CALCULATION FOR FLAT ROOF DRAINAGE. |
| | |
| | 17.[FBC R903.4]PROVIDE DRAINAGE SLOPE FOR FLAT ROOF. |
| | |
| | 18.[FBC R905.3.8]SUBMIT FLASHINF TYPE AND ATTACHMENT |
| | FOR CLAY TILE ROOF. |
| | |
| | 19. [FBC R302.6] GARAGE SPACE TO BE SEPARATED FROM |
| | HABITABLE SPACE ABV. BY NOT LESS THAN 5/8-IN. TYPE X |
| | GYPSUM BOARD OR EQUIVALENT. |
| | |
| | NOTE: |
| | ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF ADDITIONAL MATERIALS REQUESTED |