2018-06-22 12:52:49BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC R = FBC RESIDENTIAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.OK
  
 2.DRAINAGE PLAN PROVIDED NEEDS TO SHOW NUMERIC CHANGES
 IN ELEVATION THAT MEET REQUIRMENTS IN R401.3
 [FBC 107.3.5.3]LOWEST FINISHED FLOOR ELEVATION NEEDS TO
 BE ESTABLISHED SINCE IT IS NOT ON SURVEY OR PLANS.
 PIPING FROM SCUPPERS IS NOT REQUIRED IF GRADE WILL
 PROVIDE PROPER DRAINAGE. IF PIPING IS USED WE NEED TO
 SEE HOW IT IS PITCHED AND HOW IT RELEASES TO THE
 STREET.
  
 3.THE REPORT PROVIDED IS GOOD, BUT PLEASE CHOOSE ONLY
 ONE TYPE OF ICYNENE. IT IS EITHER CLASSIC OR CLASSIC
 PLUS BECAUSE THEY REQUIRE DIFFERENT THICKNESS TO
 ACHIEVE R-30.
  
 NEW COMMENTS BELOW FROM FULL REVIEW:
  
 4.[FBC R301]CHANGE ADDRESS ON SURVEY TO SAY 620 PARK
 PLACE ON BOTH SURVEY SHEETS. THE SURVEYOR PUT 618 ON
 THE SHEET SHOWING HOUSE LAYOUT.
  
 5.[FBC R311.3.1]EGRESS LANDING SHALL NOT BE LESS THAN 1
 1/2" LOWER THAN THE TOP OF THRESHOLD. PROVIDE DIMENSION
 ON SECTION TO SHOW HOW YOU ARE MEETING CODE PROVISION.
  
 6.[FBC 107.3.5.3]SHOW SECTION CUTS ON PLAN SHEET A-1 TO
 CORRESPOND TO SECTIONS ON SHEET A-6, ADD NORTH ARROW TO
 A-1, ADD ELEVATION CALLOUTS ON A-1 TO CORRESPOND TO
 ELEVATION SHEET A-2, ADD ROOF PITCH TO ELEVATIONS AND
 SECTIONS AND CONSIDER ADDING WINDOW DESIGNATIONS TO
 ELEVATION SHEET A-2 TO MATCH DESIGNATIONS ON PLAN SHEET
 A-1.
  
 7.[FBC R318]INDICATE THE MEANS OF TERMITE PROTECTION
 PROPOSED AND REFERENCE SECTION R308 FOR STANDARDS.
  
 8.[FBC R308.1]ADD NOTE FOR SHOWER ENCLOSURES TO COMPLY
 WITH SAFETY GLASS STANDARDS.
  
 9.[FBC R403.1(3) ADD NOTE TO SECTIONS SHOWING
 REINFORCING TO PROVIDE MINIMUM COVER OF 3" FOR
 REINFORCING BARS.
  
 10.[ENERGY (RE402.1.2]THE ENERGY CALCS PROVIDED SHOW
 THE WALLS TO BE RATED AT R-14 WITH INT INSULATION. HOW
 WILL THIS R-RATING BE ACHIEVED AND PROVIDE THE
 DOCUMENTATION OF THE PRODUCT. ADJUST PLANS AND ENERGY
 CALCULATIONS TO MATCH.
  
 NOTICE OF ACCEPTANCE (N.O.A.):
  
 11.PRINT DRAWING SHEETS IN LANDSCAPE FORMAT TO FIT THE
 PAGE BETTER. SOME ARE LEDIBLE, BUT SOME PRESSURE CHARTS
 ARE TOO HARD TO READ.
 THIS APPLIES TO NOA 17-1023.09, 17-0630.08 AND
 17-0614.14.
  
 12.PROVIDE 2 COPIES OF N.O.A. FOR INTENDED MULL BAR TO
 BE USED IN BEDROOM, OFFICE, MASTER BATH AND VERIFY IF
 MULL IS BEING USED IN GARAGE 2ND FL WEST ELEVATION. THE
 ELEVATION SHOWS DIFFERENT THAN THE PLAN LOFT WEST ELEV.
 2ND FL. WINDOWS.
  
 13.HIGHLIGHT ANCHOR OPTION FOR APPLICABLE BUILDING
 SYSTEM BEING USED ON WINDOW AND DOOR N.O.A.'S.
  
 14.N.O.A. 14-0506.02 IS MISSING PRESSURE DATA. PLEASE
 INSERT MISSING SHEET(S). ALSO, CHECK THAT THIS IS THE
 INTENDED DOOR TYPE FOR THE SINGLE DOORS. THE DOOR
 SCHEDULE CALLS OUT HOLLOW METAL DOORS BUT THE N.O.A IS
 FOR FIBERGLASS. UPDATE DOOR SCEDULE TO MATCH N.O.A.
 BEING USED.
  
 15.SELECT WHICH TYPE OF UNDERLAYMENT IS TO BE INSTALLED
 PER N.O.A 15-0410.04.
  
 ROOFING COMMENTS:
  
 16.[FBC R903.2.1] SUBMIT FLASHING TYPE, GAGE AND
 ATTACHMENT DETAILS. PROVIDE SCUPPER DETAIL, SIZE AND
 ROOF AREA CALCULATION FOR FLAT ROOF DRAINAGE.
  
 17.[FBC R903.4]PROVIDE DRAINAGE SLOPE FOR FLAT ROOF.
  
 18.[FBC R905.3.8]SUBMIT FLASHINF TYPE AND ATTACHMENT
 FOR CLAY TILE ROOF.
  
 19. [FBC R302.6] GARAGE SPACE TO BE SEPARATED FROM
 HABITABLE SPACE ABV. BY NOT LESS THAN 5/8-IN. TYPE X
 GYPSUM BOARD OR EQUIVALENT.
  
 NOTE:
 ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF ADDITIONAL MATERIALS REQUESTED