Plan Review Notes
Plan Review Notes For Permit 18041063
Permit Number 18041063
Review Stop P
Sequence Number 1
Notes
Date Text
2018-05-08 08:16:401ST PLUMBING REVIEW**DENIED** WITH COMMENTS NOTE - A
 COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME AND
 ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED UPON
 THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE PVC PIPE 4" IS SHOWN (A-3) IN THE PLUMBING
 ISOMETRIC AND THE FIXTURE DRAIN WILL ALLOW THE PIPE TO
 BE 3" BECAUSE OF WALL AND SPACE YOU MAY CONSIDER TO
 CHANGE THEM ACCORDING TO WHAT CODE ALLOWS. UP STAIN ON
 MAIN BUILDING YOU HAVE A WASHING MACHINE THAT SHOWS IT
 WITH AN AIR ADMITTANCE VALVE AS PER MANUFACTURES
 SPECIFICATION, IT REQUIRES A 3" SIZE PIPE ON AN AAV AND
 IT IS RECOMMENDED BY MOST WASHING MACHINES MANUFACTURE
 BECAUSE OF SOAP SUDS.
  
 2. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A
 WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS
 OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN
 ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB
 AND WHIRLPOOL BATHTUB VALVES. PLEASE SHOW LOCATION OR
 NOTE ON THE PLAN.
  
 3. ON SECOND BUILDING SHOW AN OUTSIDE SHOWER PLEASE
 LABEL AND GIVE IT MORE DETAILS. IS THERE HOT WATER
 COMING FROM THE MAIN HOUSE OR DOES THIS BUILDING HAS
 ITS OWN WATER HEATER. IF COMING UNDERGROUND TO FEED HOT
 WATER FROM THE MAIN HEATING SOURCE IT MUST BE INSULATED
 WITH AN R-3 PER FBC RE 403.5.3
  
 4. PLUMBING WATER RISER DIAGRAM REQUIRED WPB AMENDMENTS
 TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL PLUMBING
  
 5. THE LOFT HAS A NOTE FOR FUTURE PLUMBING ON THE
 SECOND FLOOR AND THERE IS A BATHROOM DOWN STAIR ON THE
 FIRST FLOOR EACH BUILDING SHALL HAVE ITS OWN VENT
 SYSTEM THOROUGH ROOF AND AN AIR ADMITTANCE VALVE WILL
 NOT BE TO CODE. OPTION ONE IS TO VENT THE DOWNSTAIRS
 BATH THROUGH THE ROOF AND LATER THE OTHER BATHROOM MAY
 BE INSTALLED OR PLUMB THE 2ND-FLOOR BATHROOM SO THE
 SYSTEM IS ALL DONE AT THAT POINT. THE VENT SYSTEM
 SERVING EACH BUILDING DRAIN SHALL HAVE NOT LESS THAN
 ONE VENT PIPE THAT EXTENDS TO THE OUTDOORS. 2017 FBC R
 3102.1 REQUIRED VENT EXTENSION.
  
 6. GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE AT THIS TIME. A GAS PLAN REVIEW
 HAS NOT BEEN PERFORMED AT THIS TIME. A SEPARATE GAS
 PERMIT AND PLANS WILL BE REQUIRED FOR A CONTRACTOR TO
 PERFORM THE RELATED WORK. PROVIDE COMPLETE PLANS AND
 GAS RISER THAT REFLECTS THE ENTIRE SCOPE OF GAS WORK TO
 BE DONE. WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  