| 2018-05-08 08:20:10 | 1ST GAS REVIEW**DENIED** WITH COMMENTS NOTE - A |
| | COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME AND |
| | ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED UPON |
| | THE RE-REVIEW OF SUBMITTED CORRECTIONS. SOME COMMENT |
| | MAY NOT APPLY BUT ARE PROVIDED FOR REFERENCES. |
| | |
| | 1. THERE IS A GAS OVEN, STOVE, TANKLESS WATER HEATER. A |
| | DRYER ON THE PLAN IS IT NOT LABELED AS GAS AND THERE IS |
| | NO ELECTRIC CIRCUIT ASSIGNED TO IT. IF IT IS GAS PLEASE |
| | CLARIFY BY LABELING ON PLAN, PAGE A-7. GAS APPLIANCES |
| | SHALL BE LISTED AND LABELED. SUBMIT MANUFACTURER?S |
| | SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS |
| | RES. SEC. G2408.1. |
| | |
| | 2. THE FIREPLACE IS IT WOOD BURNING OR FUEL, PLEASE |
| | PROVIDE MANUFACTURE SPECIFICATION AND IS IT A VENTED |
| | FIREPLACE, FBC FG R2434.1 GENERAL. |
| | |
| | 3. SUBMIT TWO COPIES FOR INSTALLATION CLEARANCES FROM |
| | THE TANKLESS INSTALLATION MANUAL. THE MANUAL REQUIRES A |
| | CLEARANCE OF EITHER 4 FEET OR 12 INCHES FROM ANY |
| | OPERABLE WINDOWS OR DOORS. SHOW THE LOCATION OF ALL |
| | OPERABLE WINDOWS AND DOORS ON THE PLAN AND THE DISTANCE |
| | OF THE TANKLESS WATER HEATER FROM EACH. WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 4. SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| | APPLIANCE. COMPLY WITH 2017 FBC FUEL GAS RES. TABLE |
| | G2413.4 (12) SCHEDULE 40 METALLIC PIPE FOR THE PROPER |
| | PIPE SIZE AND BTU LOAD. |
| | |
| | 5. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL |
| | GAS RES SECS. G2413.4.1, G2413.4.2. |
| | |
| | 6. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC |
| | SEC. 107.3.5.3 (12) RESIDENTIAL GAS. |
| | |
| | 7. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 8. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 9. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS RES. SEC. |
| | G2420.4. |
| | |
| | 10. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC |
| | FUEL GAS SEC. 402.4.1 OR 2017 FBC FUEL GAS RES. SEC. |
| | G2413.4.1. |
| | |
| | 11. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC FUEL GAS |
| | RES. SEC. G2413. |
| | |
| | 12. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| | TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING |
| | DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL GAS SECS. |
| | 502 THRU 505 OR 2017 FBC FUEL GAS RES. SECS. G2426 THRU |
| | G2429.1 |
| | |
| | 13. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL |
| | GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, & |
| | G2413.3. |
| | |
| | 14. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2017 FBC FUEL GAS RES. SEC. G2421.1. |
| | |
| | 15. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED |
| | GAS APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE |
| | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| | ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FBC R |
| | G2407.9.3. COMBINED COMBUSTION AIR AND VENTILATION AIR |
| | SYSTEM. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |