Plan Review Notes
Plan Review Notes For Permit 18041054
Permit Number 18041054
Review Stop P
Sequence Number 2
Notes
Date Text
2018-06-07 03:14:481) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS AS REQUIRED
 BY ANSI/APSP/ ICC-7 2013 SEC. 4.4.9, 4.4.9.1. THE
 MAXIMUM FLOW OF THE PUMP FROM THE PUMP CURVE IS NO
 LONGER PERMITTED TO BE USED.THE FLOW RATE SHALL BE
 DETERMINED BY USING COMPLETE SYSTEM TDH CALCULATIONS
 AND THEN LOOKING UP THE FLOW RATE USING THE
 MANUFACTURER'S CERTIFIED PUMP CURVE.2ND REQUEST.
 YOU HAVE PROVIDED THE TDH BUT WHERE ARE THE
 CALCULATIONS AS TO HOW YOU ARRIVED AT THIS NUMBER?
 2) SUBMIT TWO COPIES OF THE PUMP CURVE. THE TOTAL
 DYNAMIC HEAD MUST BE MATCHED AGAINST THE PUMP CURVE TO
 DETERMINE THE MAXIMUM SSYSTEM FLOW FOR THE SPECIFIC
 TDH. PLEASE REFER TO THE VERBIAGE IN COMMENT #1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  