| Plan Review Notes For Permit 18041054 |
| Permit Number |
18041054 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-03 08:44:57 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PLANS SHOW A SPA LOCATED IN THE CENTER OF A POOL | | | OF WATER THAT IS ONLY 6 INCHES DEEP. THE WATER HAS TO | | | BE OVER 24 INCHES DEEP IN ORDER TO MEET THE DEFINITION | | | OF A SWIMMING POOL. THIS WOULD BE CONSIDERED A WADING | | | POOL. FBC R 4501.2 | | | | | | 2) PROVIDE POOL AND SPA SECTION DETAILS THAT ACCURATELY | | | REFLECT THE PROPOSED CONSTRUCTION. SHOW THE DEPTH OF | | | THE POOL AND THE HEIGHT OF THE SPA WALLS ABOVE THE | | | SURROUNDING WADING POOL. FBC 107.2.1 |
|