2018-05-03 08:44:57PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS SHOW A SPA LOCATED IN THE CENTER OF A POOL
 OF WATER THAT IS ONLY 6 INCHES DEEP. THE WATER HAS TO
 BE OVER 24 INCHES DEEP IN ORDER TO MEET THE DEFINITION
 OF A SWIMMING POOL. THIS WOULD BE CONSIDERED A WADING
 POOL. FBC R 4501.2
  
 2) PROVIDE POOL AND SPA SECTION DETAILS THAT ACCURATELY
 REFLECT THE PROPOSED CONSTRUCTION. SHOW THE DEPTH OF
 THE POOL AND THE HEIGHT OF THE SPA WALLS ABOVE THE
 SURROUNDING WADING POOL. FBC 107.2.1