| Date |
Text |
| 2018-06-06 10:29:16 | 1) SHOW THE FIXTURE CLEARANCES OF THE PLUMBING FIXTURES |
| | ON THE FLOOR PLANS. COMPLY WITH 2017 FBCR SEC.P2705. |
| | 2) SHT.A-4.2.0.2 - DETAIL #8 - THE SHOWER SHALL BE |
| | PITCHED 1/4 OF AN INCH PER FOOT TO THE DRAIN (2% |
| | SLOPE). |
| | 3) SHT. L-1 - SPRINKLER HEADS SHALL BE LOCATED A |
| | MINIMUM OF 1 FOOT FROM THE STRUCTURE SIDEWALL PER 2017 |
| | FBCR SEC. R318. |
| | 4) SHT. P.0.0.00B - PLUMBING SPECIFICATIONS 2.00 - |
| | BASIC METHODS AND MATERIALS - NOTE # 2.1 REFERS TO THE |
| | 2014 FPC.THE CODE IN EFFECT FOR THIS PROJECT IS THE |
| | 2017 FPC. REVISE THE NOTE. |
| | 5) SHT. P.13.00B - SANITARY KEYED NOTE #2 - THE T & P |
| | VALVE DISCHARGE SHALL COMPLY WITH 2017 FBCR |
| | SEC.P2804.6.1. |
| | 6) SHT. P1.4.00B - GENERAL DOMESTIC WATER NOTE #1 |
| | REFERS TO FPC SEC.103.3(2). THERE IS NO SUCH SECTION. |
| | CLARIFY. |
| | 7) P.1.3.01B - THE WASHING MACHINE ON THE SECOND FLOOR |
| | IS NOT PERMITTED ON A WET VENT PER 2017 FBCR |
| | SEC.P3108.1 ONLY FIXTURES IN THE BATHROOM GROUP ARE |
| | PERMITTED TO DISCHARGE INTO A WET VENT. |
| | 8) P.1.3.00B - THE 2ND FLOOR MASTER BATH IS DISCHARGING |
| | 6 FIXTURE UNITS INTO A 2 INCH WET VENT. A MAXIMUM OF 4 |
| | FIXTURE UNITS SHALL DISCHARGE INTO A 2 INCH WET VENT |
| | PER 2017 FBCR TABLE P3108.3. |
| | 9) A BACKFLOW DEVICE WILL BE REQUIRED ON THE WATER |
| | SERVICE. |
| | 10) SHT. P.4.0.00B - SHOW THE SIZE OF THE EXPANSION |
| | TANK ON DETAIL #1. |
| | 11) THE MINIMUM EF RATING FOR THE WATER HEATER SHALL BE |
| | .95 PER 2017 FBC-ENERGY SEC.R403.5.6.2. |
| | 12) THE EXPANSION TANK IS NOT SHOWN ON THE WATER RISER. |
| | 13) IF THE GAS GRILL IS INSTALLED AT THE SUMMER |
| | KITCHEN, THEN A HOOD WILL BE REQUIRED OVER THE GRILL. |
| | |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | |