| 2018-06-06 06:57:57 | 1) SHT.A-1.3.01 - SHOW THE FIXTURE CLEARANCES FOR THE |
| | PLUMBING FIXTURES PER THE 2017 FBCR SEC.P2705.1. |
| | 2) SHT. A-4.2.02 - THE SHOWER FLOOR SHALL SLOPE 2% TO |
| | THE DRAIN. 2017 FBCR SEC. P2709.1. |
| | 3) SHT. L-2 - THE LAWN SPRINKLER HEADS SHALL BE LOCATED |
| | A MINIMUM OF 1 FOOT FROM THE STRUCTURE SIDEWALL PER THE |
| | 2017 FBCR SEC. R318.5. |
| | 4) SHT. P.0.0.00C - PLUMBING SPECIFICATIONS 2.00 - |
| | BASIC MATERIALS AND METHODS - NOTE #21 REFERS TO THE |
| | 2014 FBC. THE CODE IN EFFECT FOR THIS PROJECT IS THE |
| | 2017 FBC-RESIDENTIAL. |
| | 5) SHT.P.1.3.00C - SANITARY KEYED NOTES #4, #5 & #6 DO |
| | NOT CORRELATE WITH THE LOCATION SHOWN ON THE FLOOR |
| | PLAN. CLARIFY. |
| | 6) P.1.4.00C - GENERAL DOMESTIC WATER NOTE #1 REFERS TO |
| | SEC.103.3 (2) OF THE FPC. THERE IS NO SUCH CODE |
| | SECTION. CLARIFY. |
| | 7) SHT. P.2.0.00C - DETAIL #4 SIZE THE WATER RISER. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 8) SHT.P.4.0.00C - DETAIL #1 - SHOW THE SIZE OF THE |
| | EXPANSION TANK.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 9) THE MINIMUM EF RATING FOR THE WATER HEATER SHALL BE |
| | .95 PER 2017 FBC-ENERGY SEC. R403.5.6.2. SUBMIT ENERGY |
| | CALCULATIONS SHOWING COMPLIANCE. |
| | 10) SHT. P.1.3.00C - SANITARY KEYED NOTE #2 - THE T & P |
| | LINE DISCHARGE SHALL COMPLY WITH 2017 FBCR |
| | SEC.P2804.6.1. |
| | 11) SHT. P.1.4.00C - DOMESTIC WATER NOTE #1 REFERS TO |
| | SEC. 103.3 (2) IN THE FPC. THERE IS NO SUCH SECTION. |
| | CLARIFY. |
| | 12) A BACKFLOW PREVENTION DEVICE WILL BE REQUIRED ON |
| | THE WATER SERVICE. |
| | 13) THE EXPANSION TANK IS NOT SHOWN ON THE WATER RISER. |
| | 14) IF THE GAS GRILL IS INSTALLED AT THE SUMMER |
| | KITCHEN, THEN A HOOD WILL BE REQUIRED OVER THE GRILL. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |