| Plan Review Notes For Permit 18041045 |
| Permit Number |
18041045 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-07-24 10:42:38 | 1) SHT.P.3.1.00 - SHOWS A FLAT, DRY VENT DOWNSTREAM OF | | | OB-1. FLAT, DRY VENTS ARE NOT PERMITTED PER 2017 FBCR | | | SEC. P3104.3. | | | 2) SHTS. P.3.0.00 & P.3.1.00 ARE MISLABELED IN THE | | | DRAWINGS FOLDER. | | | 3) SHT.P.3.1.00 - THE SHOWER DOWNSTREAM OF THE WATER | | | CLOSET IN THE MASTER BATH IS NOT PROPERLY VENTED. THE | | | SHOWER MUST CONNECT TO THE HORIZONTAL DRAIN UPSTREAM OF | | | THE WATER CLOSET OR BE INDIVIDUALLY VENTED.2017 FBCR | | | SEC. P3101.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|