| Date |
Text |
| 2018-06-06 11:30:50 | 1) SHOW THE FIXTURE CLEARANCES OF THE PLUMBING FIXTURES |
| | ON THE FLOOR PLAN PER 2017 FBCR SEC.P2705. |
| | 2) SHT. A-4.2.0.2/DETAIL #8 - THE SHOWER SHALL BE |
| | PITCHED A 1/4 INCH PER FOOT TO THE DRAIN (2% SLOPE) PER |
| | 2017 FBCR SEC.P2709.1. |
| | 3) SHT.L-2 - SPRINKLER HEADS SHALL BE LOCATED A MINIMUM |
| | OF ONE FOOT FROM THE STRUCTURE SIDEWALL PER 2017 FBCR |
| | SEC. R318.5. |
| | 4) SHT. P.0.0.00 - PLUMBING SPECIFICATIONS 2.00 - BASIC |
| | MATERIAL & METHODS NOTE #2.1 REFERS TO THE 2014 FPC. |
| | THE CODE IN EFFECT IS THE 2017 FPC. |
| | 5) SHT. P.1.3.00 - SANITARY KEYED NOTES #4, #5, & #6 DO |
| | NOT CORRELATE WITH THE FLOOR PLAN. CLARIFY. |
| | 6) SHT. P.1.3.00 - SANITARY KEYED NOTE #2 - THE T & P |
| | VALVE DISCHARGE LINE SHALL COMPLY WITH 2017 FBCR |
| | SEC.P2804.6.1. |
| | 7) SHT. P.1.4.00 - GENERAL DOMESTIC WATER NOTE #1 |
| | REFERS TO FPC SEC.103.3(2). THERE IS NO SUCH SECTION. |
| | CLARIFY. |
| | 8) SHT. P.3.0.00 - SHOWS FLAT, DRY VENT DOWNSTREAM OF |
| | OB-1. FLAT . DRY VENTS ARE NOT PERMITTED PER 2017 FBCR |
| | SEC. P3104.3. |
| | 9) SHT. P.3.0.00 - SUBMIT AN EXPANDED SANITARY RISER. |
| | IT IS VERY DIFFICULT TO REVIEW THE RISER FOR CODE |
| | COMPLIANCE BECAUSE THE RISER LINES ARE TOO CONGESTED. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 10) SHT.P.4.0.00 - SHOW THE SIZE OF THE EXPANSION TANK |
| | ON DETAIL #1. |
| | 11) THE EXPANSION TANK IS NOT SHOWN ON THE WATER RISER. |
| | 12) IF THE GAS GRILL IS INSTALLED AT THE SUMMER |
| | KITCHEN, THEN A HOOD WILL BE REQUIRED OVER THE GRILL. |
| | 13) A BACKFLOW DEVICE WILL BE REQUIRED ON THE WATER |
| | SERVICE. |
| | 14) THE MINIMUM EF RATING FOR THE WATER HEATER SHALL BE |
| | .95 PER 2017 FBC-ENERGY SEC. R403.5.6.2. SUBMIT ENERGY |
| | CALCULATIONS SHOWING COMPLIANCE. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | |
| | |