| 2018-10-17 19:04:48 | PLAN REVIEW COMMENTS FOR TORTUGA MASTER PLAN |
| | 2ND REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) COMPLIED. |
| | |
| | 2) NOT COMPLIED. ( THE DATE OF THE CURRENT FLOOD MAPS |
| | IS OCTOBER 5, 2017 , THE COMMUNITY NUMBER IS 1200229 |
| | AND THE PLANEL NUMBER IS 0577 F. ) CORRECT THE BUILDING |
| | ELEVATION DATA ON SHEET 002 (A-0.0.01) OF THE PLANS. |
| | UPDATE THE BUILDING ELEVATION DATA ON SHEET A-0.0.01A |
| | TO REFLECT THE CURRENTLY ADOPTED FLOOD MAPS AND DATUM. |
| | AS OF OCTOBER 5TH, 2017 THE CITY HAS ADOPTED NEW FLOOD |
| | INSURANCE RATE MAPS WHICH USE NAVD 88 AS THE VERTICAL |
| | DATUM. THE CITY ALSO ADOPTED A 2' FREEBOARD WHICH |
| | REQUIRES THE FINISH FLOOR AND EQUIPMENT TO BE A MINIMUM |
| | OF TWO FEET ABOVE THE BFE. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) COMPLIED. |
| | |
| | 8) WILL COMPLY. DEFERED SUBMITTAL. PROVIDE TWO SETS OF |
| | SITE DRAINAGE PLANS FOR THE SPECIFIC LOTS WITH THE |
| | SUBMITTAL DOCUMENTS WHEN APPLYING FOR PERMITS UNDER THE |
| | MASTER. FBC 107.2.5 THE CONSTRUCTION DOCUMENTS |
| | SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE |
| | ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE |
| | AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| | GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS, |
| | FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE |
| | DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE |
| | SURVEY. IN THE CASE OF DEMOLITION, THE SITE PLAN SHALL |
| | SHOW CONSTRUCTION TO BE DEMOLISHED AND THE LOCATION AND |
| | SIZE OF EXISTING STRUCTURES AND CONSTRUCTION THAT ARE |
| | TO REMAIN ON THE SITE OR PLOT. THE BUILDING OFFICIAL IS |
| | AUTHORIZED TO WAIVE OR MODIFY THE REQUIREMENT FOR A |
| | SITE PLAN WHEN THE APPLICATION FOR PERMIT IS FOR |
| | ALTERATION OR REPAIR OR WHEN OTHERWISE WARRANTED. |
| | FBC-R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE DIVERTED |
| | TO A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF |
| | COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE |
| | GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION |
| | WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES (152 |
| | MM) WITHIN THE FIRST 10 FEET (3048 MM). |
| | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| | PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| | WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| | CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| | IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| | BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| | PERCENT AWAY FROM THE BUILDING. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) COMPLIED. |
| | |
| | 11) COMPLIED. |
| | |
| | 12) COMPLIED. |
| | |
| | 13) COMPLIED. |
| | |
| | 14) COMPLIED. |
| | |
| | 15) COMPLIED. |
| | |
| | 16) PARTIAL COMPLIANCE. (THE REQUESTED INSTALLATION |
| | INSTRUCTIONS WERE STILL NOT SUBMITTED.) THE |
| | INSTALLATION INSTRUCTIONS WERE NOT SUBMITTED. SUBMIT |
| | TWO SETS OF SPECIFICATIONS AND INSTALLATION |
| | INSTRUCTIONS FOR THE OUTDOOR RANGE AT THE OUTDOOR |
| | SUMMER KITCHEN. FBC 107.2.1 |
| | |
| | 17) COMPLIED. |
| | |
| | 18) COMPLIED. |
| | |
| | 19) COMPLIED. |
| | |
| | 20) PARTIAL COMPLIANCE. (THE REQUESTED INSTALLATION |
| | INSTRUCTIONS WERE STILL NOT SUBMITTED. THE INSTALLATION |
| | INSTRUCTIONS ACCORDING TO THE INFORMATION THAT WAS |
| | SUBMITTED FOR THIS PRODUCT IS NOA NO. 17-0821.19.) |
| | SUBMIT THE INSTALLATION INSTRUCTIONS FOR THE 8" |
| | LINTELS. SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE |
| | 8" LINTELS. FBC 107.3.4 |
| | |
| | 21) COMPLIED. |
| | |
| | 22) COMPLIED. |
| | |
| | 23) NOT COMPLIED. FOR THE ROOF TILES, SPECIFY THE |
| | FASTENER TYPE AND THE NUMBER OF FASTENERS PER TILE THAT |
| | WILL BE USED. FBC 107.2.1 THE RTA FOAM IS OKAY TO USE |
| | AT THE HIP AND RIDGES. |
| | |
| | 24) NOT COMPLIED. SUBMIT TWO SETS OF SIGNED AND SEALED |
| | TRUSS DRAWINGS AND TRUSS LAYOUT PLANS THAT HAVE BEEN |
| | REVIEWED AND APPROVED BY THE DESIGNER OF RECORD FOR THE |
| | PROJECT. FBC-R802.10 |
| | |
| | 25) NOT COMPLIED. SUBMIT TWO SETS OF PRODUCT APPROVALS |
| | FOR THE BAHAMA SHUTTERS THAT ARE SHOWN ON THE ELEVATION |
| | PLANS. FBC 107.3.4 |
| | |
| | 26) COMPLIED. |
| | |
| | 27) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | 28) THE PRODUCT APPROVALS FOR THE WINDOW MULLIONS DOES |
| | NOT HAVE THE APPROVAL STAMP OF THE DESIGNER OF RECORD. |
| | FBC 107.3.4 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |