Plan Review Notes
Plan Review Notes For Permit 18041043
Permit Number 18041043
Review Stop B
Sequence Number 3
Notes
Date Text
2018-10-17 19:04:48PLAN REVIEW COMMENTS FOR TORTUGA MASTER PLAN
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) NOT COMPLIED. ( THE DATE OF THE CURRENT FLOOD MAPS
 IS OCTOBER 5, 2017 , THE COMMUNITY NUMBER IS 1200229
 AND THE PLANEL NUMBER IS 0577 F. ) CORRECT THE BUILDING
 ELEVATION DATA ON SHEET 002 (A-0.0.01) OF THE PLANS.
 UPDATE THE BUILDING ELEVATION DATA ON SHEET A-0.0.01A
 TO REFLECT THE CURRENTLY ADOPTED FLOOD MAPS AND DATUM.
 AS OF OCTOBER 5TH, 2017 THE CITY HAS ADOPTED NEW FLOOD
 INSURANCE RATE MAPS WHICH USE NAVD 88 AS THE VERTICAL
 DATUM. THE CITY ALSO ADOPTED A 2' FREEBOARD WHICH
 REQUIRES THE FINISH FLOOR AND EQUIPMENT TO BE A MINIMUM
 OF TWO FEET ABOVE THE BFE.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) WILL COMPLY. DEFERED SUBMITTAL. PROVIDE TWO SETS OF
 SITE DRAINAGE PLANS FOR THE SPECIFIC LOTS WITH THE
 SUBMITTAL DOCUMENTS WHEN APPLYING FOR PERMITS UNDER THE
 MASTER. FBC 107.2.5 THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY. IN THE CASE OF DEMOLITION, THE SITE PLAN SHALL
 SHOW CONSTRUCTION TO BE DEMOLISHED AND THE LOCATION AND
 SIZE OF EXISTING STRUCTURES AND CONSTRUCTION THAT ARE
 TO REMAIN ON THE SITE OR PLOT. THE BUILDING OFFICIAL IS
 AUTHORIZED TO WAIVE OR MODIFY THE REQUIREMENT FOR A
 SITE PLAN WHEN THE APPLICATION FOR PERMIT IS FOR
 ALTERATION OR REPAIR OR WHEN OTHERWISE WARRANTED.
 FBC-R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE DIVERTED
 TO A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES (152
 MM) WITHIN THE FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 9) COMPLIED.
  
 10) COMPLIED.
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 13) COMPLIED.
  
 14) COMPLIED.
  
 15) COMPLIED.
  
 16) PARTIAL COMPLIANCE. (THE REQUESTED INSTALLATION
 INSTRUCTIONS WERE STILL NOT SUBMITTED.) THE
 INSTALLATION INSTRUCTIONS WERE NOT SUBMITTED. SUBMIT
 TWO SETS OF SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE OUTDOOR RANGE AT THE OUTDOOR
 SUMMER KITCHEN. FBC 107.2.1
  
 17) COMPLIED.
  
 18) COMPLIED.
  
 19) COMPLIED.
  
 20) PARTIAL COMPLIANCE. (THE REQUESTED INSTALLATION
 INSTRUCTIONS WERE STILL NOT SUBMITTED. THE INSTALLATION
 INSTRUCTIONS ACCORDING TO THE INFORMATION THAT WAS
 SUBMITTED FOR THIS PRODUCT IS NOA NO. 17-0821.19.)
 SUBMIT THE INSTALLATION INSTRUCTIONS FOR THE 8"
 LINTELS. SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 8" LINTELS. FBC 107.3.4
  
 21) COMPLIED.
  
 22) COMPLIED.
  
 23) NOT COMPLIED. FOR THE ROOF TILES, SPECIFY THE
 FASTENER TYPE AND THE NUMBER OF FASTENERS PER TILE THAT
 WILL BE USED. FBC 107.2.1 THE RTA FOAM IS OKAY TO USE
 AT THE HIP AND RIDGES.
  
 24) NOT COMPLIED. SUBMIT TWO SETS OF SIGNED AND SEALED
 TRUSS DRAWINGS AND TRUSS LAYOUT PLANS THAT HAVE BEEN
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD FOR THE
 PROJECT. FBC-R802.10
  
 25) NOT COMPLIED. SUBMIT TWO SETS OF PRODUCT APPROVALS
 FOR THE BAHAMA SHUTTERS THAT ARE SHOWN ON THE ELEVATION
 PLANS. FBC 107.3.4
  
 26) COMPLIED.
  
 27) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
 28) THE PRODUCT APPROVALS FOR THE WINDOW MULLIONS DOES
 NOT HAVE THE APPROVAL STAMP OF THE DESIGNER OF RECORD.
 FBC 107.3.4
  
  
  
  
  
  
  
  