| Plan Review Notes For Permit 18041043 |
| Permit Number |
18041043 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-08-23 17:53:07 | ROOFING SUBMITALS FOR THE CEMENT TILE ROOFING ASSEMBLY | | | IS DENIED. | | | 1) THE PRODUCT APPROVAL FOR THE ICP POLYSET RTA ROOF | | | TILE ADHESIVE, NOA NO. 16-0315.03, STATES THAT IT CAN | | | BE USED WITH ANY ROOF TILE ASSEMBLY HAVING A CURRENT | | | NOA THAT LISTS ATTACHMENT RESISTANCE VALUES WITH THE | | | USE OF ICP ADHESIVES POLYSET RTA-1. THE PRODUCT | | | APPROVAL FOR THE ENTEGRA ROOF TILE, FL7804-R10, DOES | | | NOT LIST THE POLYSET RTA-1, THEREFORE IT CAN NOT BE | | | USED FOR THIS APPLICATION. I WOULD SUGGEST THAT YOU | | | SUBMIT EITHER THE MIAMI-DADE NOA OR THE FL PRODUCT | | | APPROVALS FOR BOTH PRODUCTS AND NOT MIX THEM. | | | | | | 2) THE PRODUCT APPROVAL FOR THE GULFLOK METAL ROOFING, | | | FL#11651.9 R3 IS COMPLIANT. |
|