Plan Review Notes
Plan Review Notes For Permit 18041043
Permit Number 18041043
Review Stop P
Sequence Number 2
Notes
Date Text
2018-09-12 15:30:262ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PREVIOUS COMMENTS NOT COMPLIED:
 1) SHT. A.4.2.02 - THE SHOWER PAN LINER SHALL BE
 PITCHED 1/4 OF AN INCH PER FOOT TO THE DRAIN (2% SLOPE)
 PER 2017 FBCR- SEC. P2709.1.AND FBC PL 417.5.2
  
 7) A BACKFLOW PREVENTION DEVICE WILL BE REQUIRED ON THE
 WATER SERVICE TO THE STRUCTURE. CIVIL PLAN NOT INCLUDED
 IN SUBMITTAL. SEPARATE PERMIT REQUIRED PLACE NOTE ON
 PLAN. PER WPB UTILITIES DEPT.
  
 9) THE CODE IN EFFECT FOR THESE BUILDINGS IS THE 2017
 EDITION OF THE FBC, NOT THE 2014 AS NOTED ON THE PLANS.
 SHT P.0.0.00 UNDER PLUMBING SPECS # 1.9, 2.3 SHT.
 A.0.0.01 STILL LIST 2014 CODE
  
 NEW COMMENTS:
  
 1. IT APPEARS THAT NEW SHEETS WERE UPLOADED TO COMPLY
 WITH REVIEW COMMENTS BUT THE OLD SHEETS WERE NOT
 DELETED SO THERE ARE DUPLICATES OF THESE SHEETS
 P.0.0.00, P1.3.00, P.1.4.00, P.3.0.00, P.4.0.00 PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT. P.4.0.00 DETAIL #1 THE DISCHARGE PIPING FOR THE
 T+P VALVE SHALL DISCHARGE THROUGH AN AIR GAP LOCATED IN
 THE SAME ROOM AS THE WATER HEATER. AND OR DISCHARGE TO
 THE FLOOR OR TO THE PAN COMPLY WITH FBC RES P2804.6.1
  
 3. PLEASE PROVIDE A SANITARY ISOMETRIC DRAWING. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  