Plan Review Notes
Plan Review Notes For Permit 18041043
Permit Number 18041043
Review Stop B
Sequence Number 2
Notes
Date Text
2018-08-23 18:00:39PLAN REVIEW COMMENTS FOR TORTUGA MASTER PLAN
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT COMPLIED. SEE SHEET 002 (A-0.0.01). UPDATE
 BUILDING CODE DATA AND APPLICABLE CODES ON THE PLANS TO
 THE 2017 FBC SIXTH EDITION. THE PLANS HAVE SEVERAL
 REFERENCES TO THE FBC FIFTH EDITION (2014). THE FBC
 SIXTH EDITION (2017) WENT INTO EFFECT ON JANUARY 1,
 2018. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT DATE
 ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC SIXTH
 EDITION (2017). FS CHAPTER 553
  
 2) NOT COMPLIED. CORRECT THE BUILDING ELEVATION DATA ON
 SHEET 002 (A-0.0.01) OF THE PLANS. UPDATE THE BUILDING
 ELEVATION DATA ON SHEET A-0.0.01A TO REFLECT THE
 CURRENTLY ADOPTED FLOOD MAPS AND DATUM. AS OF OCTOBER
 5TH, 2017 THE CITY HAS ADOPTED NEW FLOOD INSURANCE RATE
 MAPS WHICH USE NAVD 88 AS THE VERTICAL DATUM. THE CITY
 ALSO ADOPTED A 2' FREEBOARD WHICH REQUIRES THE FINISH
 FLOOR AND EQUIPMENT TO BE A MINIMUM OF TWO FEET ABOVE
 THE BFE.
  
 3) NOT COMPLIED.THE FIRE RESISTANCE RATING REQUIREMENTS
 ON SHEET 002 ( A-0.0.01) IS MISLEADING WITHOUT THE
 REQUIRED MINIMUM FIRE SEPARATION BEING PROVIDED. SEE
 FBCR TABLE R302.1.
  
 4) NOT COMPLIED. FBC- R310.2 IS THE CODE SECTION FOR
 EMERGENCY ESCAPE AND RESCUE IN THE 2017 FBC SIXTH
 EDITION. THE CODE SECTION PROVIDED ON SHEET 002
 (A-0.0.01) OF THE PLANS IS INCORRECT. FBC 107.2.1
  
 5) NOT COMPLIED. THE NOTE UNDER EXTERIOR OPENINGS ON
 SHEET 002 ( A-0.0.01) IS NOT WORDED CORRECTLY. FBC
 R311.3.2 STATES THAT THE LANDINGS AT EXTERIOR DOORS
 SHALL NOT BE MORE THAN 7-3/4 INCHES BELOW THE TOP OF
 THE THRESHOLD.
  
 6) COMPLIED. WORST-CASE ENERGY FORM SUBMITTED FOR
 MASTER. LOT SPECIFIC ENERGY CODE COMPLIANCE DOCUMENTS
 TO BE SUBMITTED WITH INDIVIDUAL LOT PERMITS.
  
 7) NOT COMPLIED. THE 2014 EDITION IS REFERENCED ON THE
 ATTIC VENTILATION ANALYSIS ON SHEET A-1.4.01. PLEASE
 UPDATE TO THE 2017 FBC.
  
 8) DEFERED SUBMITTAL. PROVIDE TWO SETS OF SITE DRAINAGE
 PLANS FOR THE SPECIFIC LOTS WITH THE SUBMITTAL
 DOCUMENTS WHEN APPLYING FOR PERMITS UNDER THE MASTER.
 FBC 107.2.5 THE CONSTRUCTION DOCUMENTS SUBMITTED WITH
 THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A
 SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW
 CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES AND, AS APPLICABLE,
 FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN FLOOD
 ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE BOUNDARY LINE SURVEY. IN THE CASE OF
 DEMOLITION, THE SITE PLAN SHALL SHOW CONSTRUCTION TO BE
 DEMOLISHED AND THE LOCATION AND SIZE OF EXISTING
 STRUCTURES AND CONSTRUCTION THAT ARE TO REMAIN ON THE
 SITE OR PLOT. THE BUILDING OFFICIAL IS AUTHORIZED TO
 WAIVE OR MODIFY THE REQUIREMENT FOR A SITE PLAN WHEN
 THE APPLICATION FOR PERMIT IS FOR ALTERATION OR REPAIR
 OR WHEN OTHERWISE WARRANTED.
 FBC-R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE DIVERTED
 TO A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES (152
 MM) WITHIN THE FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 9) COMPLIED.
  
 10) NOT COMPLIED. SPECIFY ON THE PLANS. SHOW COMPLIANCE
 WITH FBC-R318.1 R318.1 TERMITE PROTECTION. TERMITE
 PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES,
 BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION. SEE SECTION 202, REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF THE TERMITE
 PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL
 BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED
 PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING
 STATEMENT: THE BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES.
 TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE
 AND CONSUMER SERVICES.
  
 11) COMPLIED.
  
 12) NOT COMPLIED. IN ADDITION TO THE SQUARE FOOT AREAS
 OF THE CONDITIONED SPACE, PROVIDE THE AREAS OF THE
 GARAGE, PORCHES AND ANY OTHER SPACES THAT DO NOT
 CONDITION AIR. PROVIDE ACCURATE AREA TABULATIONS FOR
 EACH FLOOR LISTING BOTH CONDITIONED AND UN-CONDITION
 SPACES ON THE FLOOR PLANS. FBC 107.2.1
  
 13) NOT COMPLIED. FBC 107.2.1.2 SINCE THE WINDOW AND
 DOOR PRESSURES ON THE PRODUCT APPROVALS ARE BASED ON
 VASD AND IN ORDER TO AVOID CONFUSION, PLEASE PROVIDE A
 COMPONENT AND CLADDING SCHEDULE WITH 132MPH EXPOSURE C
 NOMINAL VASD PRESSURES. FBC 301.2.1.3
  
 14) COMPLIED.
  
 15) COMPLIED.
  
 16) PARTIAL COMPLIANCE. THE INSTALLATION INSTRUCTIONS
 WERE NOT SUBMITTED. SUBMIT TWO SETS OF SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE OUTDOOR RANGE AT
 THE OUTDOOR SUMMER KITCHEN. FBC 107.2.1
  
 17) COMPLIED.
  
 18) COMPLIED.
  
 19) COMPLIED.
  
 20) PARTIAL COMPLIANCE. SUBMIT THE INSTALLATION
 INSTRUCTIONS FOR THE 8" LINTELS. SUBMIT TWO SETS OF
 PRODUCT APPROVALS FOR THE 8" LINTELS. FBC 107.3.4
  
 21) NOT COMPLIED. SEE MARKUP ON SHEET A-6.2.01. THE
 PRODUCT APPROVAL NUMBERS LISTED ON THE PLANS FOR THE
 OVERHEAD GARAGE DOORS ARE FL NUMBERS NOT NOAS. PLEASE
 CORRECT.
  
 22) COMPLIED.
  
 23) NOT COMPLIED. THE PRODUCT APPROVAL FOR THE ICP
 POLYSET RTA ROOF TILE ADHESIVE, NOA NO. 16-0315.03,
 STATES THAT IT CAN BE USED WITH ANY ROOF TILE ASSEMBLY
 HAVING A CURRENT NOA THAT LISTS ATTACHMENT RESISTANCE
 VALUES WITH THE USE OF ICP ADHESIVES POLYSET RTA-1. THE
 PRODUCT APPROVAL FOR THE ENTEGRA ROOF TILE, FL7804-R10,
 DOES NOT LIST THE POLYSET RTA-1, THEREFORE IT CAN NOT
 BE USED FOR THIS APPLICATION. I WOULD SUGGEST THAT YOU
 SUBMIT EITHER THE MIAMI-DADE NOA OR THE FL PRODUCT
 APPROVALS FOR BOTH PRODUCTS AND NOT MIX THEM.
 INDICATE THE CEMENT ROOF TILE AND ATTACHMENT METHOD
 THAT WILL BE USED BY MARKING THE APPROPRIATE
 INFORMATION ON THE PLANS. FBC 107.2.1 IF AN ADHESIVE
 WILL BE USED, SUBMIT THE PRODUCT APPROVAL FOR IT. FBC
 107.3.4 IF A MORTAR OR ADHESIVE SET IS USED SUBMIT THE
 PRODUCT APPROVAL FOR THE UNDERLAYMENT TO SHOW THAT IT
 WILL MEET WINDLOADS. SEE INSTALLATION NOTE 6.2 ON PAGE
 5 OF THE TILE PRODUCT APPROVAL.
  
 24) NOT COMPLIED. SUBMIT TWO SETS OF SIGNED AND SEALED
 TRUSS DRAWINGS AND TRUSS LAYOUT PLANS THAT HAVE BEEN
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD FOR THE
 PROJECT. FBC-R802.10
  
 25) NOT COMPLIED. SUBMIT TWO SETS OF PRODUCT APPROVALS
 FOR THE BAHAMA SHUTTERS THAT ARE SHOWN ON THE ELEVATION
 PLANS. FBC 107.3.4
  
 26) COMPLIED.
  
 27) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  