| 2018-06-05 13:22:28 | 1) SHT. A.4.2.02 - THE SHOWER SHALL BE PITCHED 1/4 OF |
| | AN INCH PER FOOT TO THE DRAIN (2% SLOPE) PER 2017 FBCR- |
| | SEC. P2709.1. |
| | 2) SHT. A-1.3.0.2 - THE FIXTURE CLEARANCES IN THE |
| | BATHROOMS SHALL COMPLY WITH 2017 FBCR SEC. P2705. |
| | 3) SHT. L.2 - SPRINKLER HEADS SHALL BE LOCATED A |
| | MINIMUM OF ONE FOOT FROM THE STRUCTURE SIDEWALL PER |
| | 2017 FBCR SEC. R318.5. |
| | 4) SHT. P.1.3.00 A- SANITARY KEYED NOTES - NOTE #2 - |
| | THE T & P DISCHARGE SHALL COMPLY WITH 2017 FBCR SEC. |
| | P2804.6.1. |
| | 5) SHT. P.1.3.00A - KEYED NOTES #4, #5 & #6 DO NOT |
| | CORRELATE WITH THE LOCATION ON THE FLOOR PLAN. |
| | 6) P1.4.00A - GENERAL DOMESTIC WATER NOTE #1 REFERS TO |
| | SEC. 103.3 (2). THERE IS NO SUCH SECTION IN THE |
| | PLUMBING CODE. CLARIFY. |
| | 7) A BACKFLOW PREVENTION DEVICE WILL BE REQUIRED ON THE |
| | WATER SERVICE TO THE STRUCTURE. |
| | 8) P.4.0.00A - DETAIL #1 - SHOW THE SIZE OF THE |
| | EXPANSION TANK ON THE DETAIL. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 9) THE CODE IN EFFECT FOR THESE BUILDINGS IS THE 2017 |
| | EDITION OF THE FBC, NOT THE 2014 AS NOTED ON THE PLANS. |
| | 10) THE MINIMUM EF RATING FOR THE WATER HEATER SHALL BE |
| | .95 PER THE 2017 FBC-ENERGY SEC. R403.5.6.2. SUBMIT |
| | ENERGY CALCULATIONS SHOWING COMPLIANCE. |
| | 11) THE EXPANSION TANK IS NOT SHOWN ON THE WATER RISER. |
| | 12) IF THE GAS GRILL IS INSTALLED AT THE SUMMER |
| | KITCHEN, THEN A HOOD WILL BE REQUIRED OVER THE GRILL. |
| | |
| | |