| Plan Review Notes For Permit 18041031 |
| Permit Number |
18041031 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-07-05 15:02:35 | 1) INDICATE THE CEMENT ROOF TILE AND ATTACHMENT METHOD | | | THAT WILL BE USED BY MARKING THE APPROPRIATE | | | INFORMATION ON THE PLANS. FBC 107.2.1 IF AN ADHESIVE | | | WILL BE USED, SUBMIT THE PRODUCT APPROVAL FOR IT. FBC | | | 107.3.4 IF A MORTAR OR ADHESIVE SET IS USED SUBMIT THE | | | PRODUCT APPROVAL FOR THE UNDERLAYMENT TO SHOW THAT IT | | | WILL MEET WINDLOADS. SEE INSTALLATION NOTE 6.2 ON PAGE | | | 5 OF THE TILE PRODUCT APPROVAL. | | | | | | |
|