| 2018-06-30 08:02:35 | 1) THE MINIMUM EF RATING FOR THE WATER HEATER SHALL BE | | | .95 PER THE 2017 FBC - ENERGY SEC. R403.5.6.2. SUBMIT | | | ENERGY CALCULATIONS SHOWING COMPLIANCE. NOTE: AS OF | | | APRIL 16, 2015 THE DOE HAS REVISED THE EQUATION FOR | | | DETERMINING THE MINIMUM EF RATING FOR ELECTRIC WATER | | | HEATERS. THIS REVISED EQUATION WAS NOT REVISED IN THE | | | 2017 FBC-ENERGY. THIS COMMENT HAS NOT BEEN ADEQUATELY | | | ADDRESSED.2ND REQUEST. | | | 2) PLACE NOTE ON THE IRRIGATION PLANS THAT SPRINKLER | | | HEADS SHALL BE LOCATED A MINIMUM OF ONE FOOT FROM THE | | | STRUCTURE SIDEWALL PER 2017 FBCR SEC.R318.5. 2ND | | | REQUEST. | | | 3) A BACKFLOW PREVENTER WILL BE REQUIRED ON THE WATER | | | SERVICE AT THE METER PER THE CITY OF WPB CROSS | | | CONNECTION CONTROL MANUAL. THE RESPONSE NARRATIVE | | | REFERS TO CIVIL DRAWING BUT THERE ARE NO CIVIL PLANS IN | | | THIS SET. PLACE A NOTE ON SHT.P.1.4.00 THAT A BACKFLOW | | | DEVICE WILL BE INSTALLED IN ACCORDANCE WITH THE CITY OF | | | WPB CROSS CONNECTION CONTROL MANUAL. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|