| 2018-07-05 13:04:28 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18041031 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC R = FBC RESIDENTIAL |
| | |
| | **NOTE THAT RESPONSE LETTER ENDS AT ITEM 16. |
| | |
| | 1. SHEET A-0.0.01A WAS UPDATED TO SAY 2017, BUT IT |
| | STILL SAY FIFTH EDITION. WE ARE CURRENTLY USING THE |
| | SIXTH EDITION. |
| | ALSO, UPDATE SHEET A.3.2.01 GUTTER DETAIL REFERS TO OLD |
| | CODE. |
| | |
| | 2. OK |
| | |
| | 3. WHY SHOW 1HR RATING WHEN YOU MAKE SEPARATION |
| | DISTANCE TO USE ZERO HOURS? IF USING 1 HR SHOW UL WALL |
| | ASSEMBLE TO ACHIEVE THE SPECIFIED RATING. |
| | THE CODE REFERENCE ON SHEET A-0.0.01A FIRE RESISTANCE |
| | RATING REQUIREMENTS, THE CODE REFERENCE FBC R3.2.01 |
| | SHOULD READ FBC R302.1 |
| | |
| | 4-5. OK |
| | |
| | 6. ENERGY CALCULATIONS DATA SHEET SAYS 2 BEDROOMS. |
| | PLEASE UPDATE TO 3 BEDROOM. |
| | CROSS VENTILATION BOX SHOULD INDICATE "YES" CROSS |
| | VENTIALLATION BEING UTILIZED. |
| | [FBC ENERGY R402.1.2]GLAZING SHGC LEVELS FOR WINDOW A&B |
| | EXCEED ALLOWABLE VALUES IN TABLE R402.1.2 OF THE |
| | RESIDENTIAL ENERGY CODE FOR CLIMATE ZONE 1. |
| | CHECK MARKS AS APPLICABLE TO MANDATORY CHECKLIST. |
| | |
| | [FBC 302.10]PROVIDE CUT SHEET FOR THE PROPOSED |
| | INSULATION TO SHOW FLAME SPREAD INDEX, OR INDICATE THAT |
| | THEY WILL BE PROVIDED AS SUBMITTAL PRIOR TO |
| | INSTALLATION. |
| | SHOW IN PLAN SECTIONS,DETAILS AND WALL TYPES THE |
| | INSULATION BEING USED ,INCLUDING R-VALUE, SO IT IS NOT |
| | JUST REFERENCING "SEE ENERGY CALCS". |
| | [FBC R806.3]IF BLOWN IN INSULATION IS BEING USED, HOW |
| | WILL YOU PREVENT IT FROM BLOCKING CROSS VENTILLATION? |
| | SHOW/EXPLAIN ON PLANS. |
| | |
| | 7-11. OK |
| | |
| | 12. PARTIALLY ADDRESSED. ADD CRICKET DETAIL TO SECTIONS |
| | A-3.2.01 TO SHOW THAT CRICKET WILL BE ON BACK SIDE OF |
| | TOWER AS WELL AS SIDE. |
| | |
| | 13-14. OK |
| | |
| | 15. ADD NOTE THAT TYPICAL TRUSS ATTACHMENT USES TYPE |
| | "1" STRAP, OR LABEL EACH TRUSS TO SHOW EACH TRUSSES |
| | CONNECTOR DESIGNATION. |
| | |
| | 16. OK |
| | |
| | ***COMMENT RESPONSE SHEET ENDED AT 16.*** |
| | |
| | IN RE-SUBMITTAL PLEASE INCLUDE NEW RESPONSE SHEET FOR |
| | ALL COMMENTS. |
| | |
| | 17) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL |
| | MULLIONS AND EXTERIOR DOOR TYPES. |
| | |
| | 18) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE |
| | OUTDOOR STONE VENEER FACING. FBC 107.3.4 |
| | |
| | 19) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE OFF |
| | RIDGE ROOF VENTS (NOA 17-1031.03). FBC 107.3.4 |
| | |
| | 20) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE 8" |
| | LINTELS. FBC 107.3.4 |
| | |
| | 21) THE PRODUCT APPROVAL NUMBERS LISTED ON THE PLANS |
| | FOR THE OVERHEAD GARAGE DOORS ARE FL NUMBERS NOT NOAS. |
| | PLEASE CORRECT. |
| | |
| | 22) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | ENTRY DOOR HAVE A DIFFERENT NUMBER THAN THE ONE |
| | SPECIFIED ON THE PLANS. FL17-1031.03 IS LISTED ON THE |
| | PLANS. THIS IS A NOA NUMBER NOT AN FL. THE PRODUCT |
| | APPROVAL SUBMITTED IS FL15037.3. PLEASE COORDINATE. FBC |
| | 107.2.1 |
| | -01 DOOR ENTRY. MATCH N.O.A. NUMBER ON PLANS SHEET |
| | A-6.2.01 DOOR TYPE "C" TO MATCH THE N.O.A. |
| | PROVIDED(FL15037.3). |
| | |
| | 23) INDICATE THE CEMENT ROOF TILE AND ATTACHMENT METHOD |
| | THAT WILL BE USED BY MARKING THE APPROPRIATE |
| | INFORMATION ON THE PLANS. FBC 107.2.1 IF AN ADHESIVE |
| | WILL BE USED, SUBMIT THE PRODUCT APPROVAL FOR IT. FBC |
| | 107.3.4 IF A MORTAR OR ADHESIVE SET IS USED SUBMIT THE |
| | PRODUCT APPROVAL FOR THE UNDERLAYMENT TO SHOW THAT IT |
| | WILL MEET WINDLOADS. SEE INSTALLATION NOTE 6.2 ON PAGE |
| | 5 OF THE TILE PRODUCT APPROVAL. |
| | PROVIDE N.O.A.'S FOR UNDERLAYMENT MATERIALS FOR CEMENT |
| | TILE ROOF. |
| | |
| | |
| | 24) SUBMIT TWO SETS OF SIGNED AND SEALED TRUSS DRAWINGS |
| | AND TRUSS LAYOUT PLANS THAT HAVE BEEN REVIEWED AND |
| | APPROVED BY THE DESIGNER OF RECORD FOR THE PROJECT. |
| | FBC-R802.10 |
| | |
| | 25) PRODUCT APPROVALS WERE SUBMITTED FOR FIXED WINDOWS |
| | (NOA NO. 17-1212.13) AND STRUCTURAL MULLIONS (NOA NO. |
| | 17-1212.24) AND NEITHER OF THESE ARE USED FOR THIS |
| | PROJECT. PLEASE CLARIFY. FBC 107.2.1 |
| | NOT ADDRESSED. REMOVE N.O.A.'S IF NOT BEING USED. |
| | |
| | 26. IN RE-SUBMITTAL PLEASE INCLUDE NEW RESPONSE SHEET |
| | FOR ALL COMMENTS. |
| | |
| | 27. [FBC R302.11]ADD FIREBLOCKING TO DETAIL ON TYPICAL |
| | WALL SECTION. |
| | |
| | 28. [FBC 302.3.1] IT IS SUGGESTED TO ADD A NOTE TO DOOR |
| | SCEHDULE TO SHOW WHAT IS BEING PROVIDED FOR DOOR 116C. |
| | |
| | NOTE: |
| | ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | PLEASE PROVIDE TWO IDENTICAL COPIES OF ALL ITEMS |
| | SUBMITTED. |
| | |
| | |
| | |
| | |
| | |