2018-06-05 11:19:381) SHT. A.4.2.02 - THE SHOWER SHALL BE PITCHED 1/4 OF
 AN INCH PER FOOT TO THE DRAIN (2% SLOPE) PER 2017 FBCR-
 SEC. P2709.1.
 2) SHT. A.4.2.04 - THE FIXTURE CLEARANCES IN THE
 BATHROOMS SHALL COMPLY WITH 2017 FBCR SEC. P2705.
 3) SHT. L.2 - SPRINKLER HEADS SHALL BE LOCATED A
 MINIMUM OF ONE FOOT FROM THE STRUCTURE SIDEWALL PER
 2017 FBCR SEC.R318.5.
 4) SHT. P.1.3.00 - SANITARY KEYED NOTES - NOTE #2 - THE
 T & P DISCHARGE SHALL COMPLY WITH 2017 FBCR SEC.
 P2804.6.1.
 5) SHT. P.1.3.00 - KEYED NOTE #8 - REFERENCES TABLE
 701.1 (1) IN THE FPC. THERE IS NO SUCH TABLE. CLARIFY.
 6) P1.4.00 - GENERAL DOMESTIC WATER NOTE #1 REFERS TO
 SEC. 103.3 (2). THERE IS NO SUCH SECTION IN THE
 PLUMBING CODE. CLARIFY.
 7) A BACKFLOW PREVENTION DEVICE WILL BE REQUIRED ON THE
 WATER SERVICE TO THE STRUCTURE.
 8) SHT. P.1.3.00 - NOTE #8 NOTES FUTURE 3 INCH LINE TO
 BE CAPPED FOR FUTURE USE. AN AUTOMATIC CLOTHES WASHER
 CONNECTION SHALL BE PROVIDED PER TABLE 403.1 OF THE
 FBC-PLUMBING.
 9) P.4.0.00 - DETAIL #1 - SHOW THE SIZE OF THE
 EXPANSION TANK ON THE DETAIL. WPB AMEND. TO FBC SEC.
 107.2.1.
 10) THE CODE IN EFFECT FOR THESE BUILDINGS IS THE 2017
 EDITION OF THE FBC, NOT THE 2014 AS NOTED ON THE PLANS.
 11) THE MINIMUM EF FOR THE WATER HEATER SHALL BE .95
 PER 2017 FBC-ENERGY SEC. R403.5.6.2. SUBMIT ENERGY
 CALCULATIONS SHOWING COMPLIANCE.
 12) THE EXPANSION TANK IS NOT SHOWN ON THE WATER RISER.
 13) IF THE GAS GRILL IS INSTALLED AT THE SUMMER
 KITCHEN, THEN A HOOD WILL BE REQUIRED OVER THE GRILL.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  