| 2018-07-30 18:38:33 | |
| | |
| | REMAINDER: |
| | MASTER PERMIT WAS APPROVED WITH PROVISO. PROVIDE |
| | REQUIRED INFORMATION PRIOR TO INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. FEB. 16/ 2018 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) NEW OUTSWING STOREFRONT DOORS AND TRANSOM TO BE A |
| | DEFERRED SUBMITTAL. SHEET A-4 DETAIL D4/A-4 INDICATES A |
| | NEW STOREFRONT GLAZING SYSTEM, DOOR, TRANSOM AND FRAME. |
| | A FLORIDA PRODUCT APPROVAL IS TO BE REVIEWED BY THE |
| | DESIGN PROFESSIONAL BEFORE BEING SUBMITTED TO THE |
| | JURISDICTION HAVING JURISDICTION FOR APPROVAL AND |
| | BEFORE INSTALLATION. THIS REVIEW SHOP DRAWINGS WERE |
| | SUBMITTED NO PRODUCT APPROVAL. |
| | |
| | 107.3.4.2 DEFERRED SUBMITTALS. DOCUMENTS FOR DEFERRED |
| | SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL |
| | REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL |
| | WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 2) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION. |
| | 2014 FBC-B 2204.1 WELDING |
| | 2014 FBC-B 2204.2 BOLTING. |
| | |