| 2018-04-24 16:31:28 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ELECTRICAL PERMIT APPLICATION IS REQUIRED FOR THE |
| | SUB-PERMIT. PROVIDE ELECTRICAL PERMIT APPLICATION. WPB |
| | FBC 105.1 |
| | 2. PER LETTER IN FILES FROM VINCENT VECCHARELLA, |
| | ELECTRICAL WAS NOT INCLUDED IN THE ORIGINAL PERMIT |
| | APPLICATION. THEREFORE, THE COST OF MATERIALS AND LABOR |
| | FOR THIS INSTALLATION MUST BE STATED ON PERMIT |
| | APPLICATION. THE REVISION STATES THAT THERE IS NO |
| | INCREAS IN VALUE FOR THIS WORK, BUT THERE WOULD |
| | OBVIOUSLY BE COST ASSOCIATED WITH THIS. PROVIDE COPY OF |
| | SIGNED CONTRACT WITH SCOPE AND VALUE OF WORK, TO |
| | INCLUDE ALL MATERIALS AND LABOR. FBC 109.3 |
| | 3. PROVIDE LOAD CALCULATION FOR TRAILER. NEC 220 |
| | 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 5. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| | NEC 110.3, 110.9 |
| | 6. PROVIDE SITE PLAN SHOWING LOCATION OF SERVICE. WPB |
| | FBC 107.2.1 |
| | 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 8. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |