| 2018-05-30 10:26:35 | |
| | 1) SHT. A100 - THE PLAN REFERS TO THE EPCOT |
| | ACCESSIBILITY CODE AND THE EPCOT BUILDING CODE. HOW ARE |
| | THESE CODES APPLICABLE TO THIS PROJECT? CLARIFY. |
| | |
| | 2.) AS THE ORIGINAL PERMIT WAS FOR "TEMPORARY |
| | CONSTRUCTION TRAILERS" WHICH ARE EXEMPT FROM FLORIDA |
| | BUILDING CODE, BUT ACTUAL USE IS AS A BAR |
| | (18021163/18041013), COMPLIANCE WITH ALL REQUIREMENTS |
| | OF THE FLORIDA BUILDING IS REQUIRED. A DESIGN |
| | PROFESSIONAL IS REQUIRED TO PROVIDE ALL INFORMATION, |
| | FS481. A SKETCH AND "MODSPACE" DRAWING WERE PROVIDED; |
| | THIS CANNOT BE USED TO DEMONSTRATE CODE COMPLIANCE. AN |
| | INCOMPLETE "LIFE SAFETY PLAN" WAS SUBMITTED; PLEASE |
| | REVISE THIS PLAN TO ADDRESS COMMENTS, OR HAVE ANOTHER |
| | DESIGN PROFESSIONAL PREPARE A PLAN. |
| | |
| | 3.) PROVIDE DOCUMENTATION OF DBPR APPROVAL FOR THIS |
| | MODULAR STRUCTURE. 2017 FBC SEC. 458.4.2. |
| | |
| | 4) SHT. A100 - THE DESIGN PROFESSIONAL IS TO DETERMINE |
| | PROPOSED OCCUPANCY CLASSIFICATION, OCCUPANT LOAD. AS |
| | PROPOSED USE IS NOT CONSISTENT WITH THE DCA APPROVAL, |
| | MODIFICATIONS MAY BE REQUIRED IF DCA MODULAR WAS NOT |
| | DESIGNED FOR USE AS A BAR. |
| | |
| | 5.) A PLAN WAS PROVIDED; IT APPEARS THAT THE DCA |
| | MODULAR WAS MODIFIED. PROVIDE A PLAN SHOWING WHAT WORK |
| | WAS DONE TO ADAPT A MODULAR DESIGNED AS BUSINESS TO A |
| | BAR, FBC 107. |
| | |
| | 6.) PROVIDE A DETAIL FOR THE BAR WHICH SHOWS COMPLIANCE |
| | WITH FBC-ACCESS. SEC. 902. |
| | |
| | 7.) A VALUE OF $0 WAS PROVIDED FOR THIS REVISION. |
| | PROVIDE CONTRACT AMOUNT, FBC 109. |
| | |
| | 8). DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS |
| | PER F.A.C. RULE 61G15-23.001. DCA MODULAR PLANS ARE ON |
| | FILE WITH THE STATE, SO SIGNED AND SEALED ORIGINALS |
| | SHOULD NOT BE SUBMITTED (DCA PLANS ONLY), BUT THE STATE |
| | APPROVED STAMPED PLANS FROM THE WEBSITE SHOULD BE |
| | SUBMITTED. |
| | |
| | 9) A GREASE CONTROL DEVICE WILL BE REQUIRED FOR THE |
| | SINKS IN THE BAR AREA PER 2017 FBC-PLUMBING SEC. |
| | 1003.1. |
| | |
| | 10) SHOW THE LENGTH AND WIDTH DIMENSIONS OF THE TOILET |
| | ROOM. WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 11) SHOW THE REQUIRED CLEAR SPACES FOR THE WATER CLOSET |
| | AND THE LAVATORY ON THE PLANS. COMPLY WITH 2017 |
| | FBC-ACCESS. SECS. 604.3, 606.2. |
| | |
| | 12) SHOW THE REQUIRED FIXTURE CLEARANCES PER THE 2017 |
| | FBC-PLUMBING AND FBC-ACCESS. SEC.604.2. |
| | |
| | 13) SUBMIT ELEVATION DETAILS FOR ALL THE HANDICAP |
| | ACCESSIBILITY COMPONENTS IN THE TOILET ROOM (GRAB BARS, |
| | HEIGHT OF WATER CLOSET AND LAVATORY, TOILET PAPER |
| | DISPENSER, MIRROR, ETC.) |
| | |
| | 14) THE LAVATORY SHALL BE PROVIDED WITH KNEE AND TOE |
| | CLEARANCE PER 2017 FBC SEC.306. |
| | |
| | 15) SHOW THE REQUIRED TURNING SPACE IN THE TOILET ROMM |
| | PER 2017 FBC-ACCESS. SEC.304. |
| | |
| | 16) AT LEAST 5 PERCENT OF THE TABLES SHALL COMPLY WITH |
| | SEC. 902 OF 2017 FBC-ACCESS. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | |
| | |