2018-07-06 10:48:08PERMIT # 18041012
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PER PLANS PROVIDED, OCCUPANCY LOAD OF EACH TRAILER
 IS 14 PERSONS, MAXIMUM. ALTERATIONS TO THIS OCCUPANCY
 LOAD SHALL BE REQUESTED IN WRITING, AND SUBMITTED TO
 THE OFFICE OF THE FIRE MARSHAL FOR APPROVAL.
  
 2) PER PLANS PROVIDED, THE "INTENDED OCCUPANCY LOAD" OF
 THE DECK AREA IS SET AT 65 PERSONS AND IS HEREBY THE
 APPROVED OCCUPANCY LOAD. THE "DESIGNED OCCUPANCY LOAD"
 OF 190 PERSONS DOES NOT APPEAR TO COMPLY WITH ANY OF
 THE OCCUPANT LOAD FACTORS AS LISTED UNDER NFPA 101,
 CHAPTER 7. OCCUPANT LOAD OF 190 IS NOT APPROVED.
  
 3) THE PROVIDED SEATING/FURNITURE PLAN OF 4 TABLES AND
 16 CHAIRS IS THE APPROVED FURNITURE PLAN FOR THE DECK
 AREA. ALTERATIONS TO THIS FURNITURE PLAN SHALL BE
 REQUESTED IN WRITING, AND SUBMITTED TO THE OFFICE OF
 THE FIRE MARSHAL FOR APPROVAL.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL