2018-05-10 13:29:14PERMIT # 18041012
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) THE WOOD PLATFORM CURRENTLY IN PLACE TO CONNECT ALL
 THREE TRAILERS IS CONSIDERED A STRUCTURE AND THEREFORE,
 DOES NOT MEET THE SEPERATION REQUIREMENTS OF THE CODE
 REFERENCED BELOW.
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 2) PLEASE PROVIDE THE DETAILS REGARDING THE MATERIAL
 USED FOR THE PLATFORM. IS THE MATERIAL FIRE RETARDENT
 OR HAS IT BEEN TREATED WITH FIRE RETARDENT? PLEASE
 INCLUDE THE MANUFACTURER'S SPECIFICATIONS FOR THE
 MATERIAL AND/OR THE FIRE RETARDENT USED.
  
 3)A FIRE FINAL (131) INSPECTION IS REQUIRED FOR THIS
 PERMIT. BECAUSE THE TRAILER IS ALREADY INSTALLED AND IN
 USE, THE INSPECTION SHALL BE SCHEDULED (VIA THE
 AUTOMATED PERMIT SCHEDULING SYSTEM) IMMEDIATELY UPON
 ISSUANCE OF THIS PERMIT.
  
 4) THE MASTER PERMIT (18021162) IS FOR THE INSTALLATION
 OF A CONSTRUCTION TRAILER. THERE IS NO PERMIT ISSUED
 FOR THE INSTALLATION OF THE 76X48 FOOT PLATFORM. PLEASE
 ENSURE THAT IF ONE IS REQUIRED, PER THE FBC, THAT IT IS
 APPLIED FOR AND OBTAINED.
  
 5) PLEASE PROVIDE THE OCCUPANT LOAD CALCULATION AND
 TOTAL OCCUPANT LOAD FOR THIS TRAILER. PLEASE NOTE THAT
 OCCUPANCY EXCEEDING 49 PERSONS REQUIRES PANIC HARDWARE
 ON ALL MEANS OF EGRESS DOORS.
  
 6) EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751