Plan Review Notes
Plan Review Notes For Permit 18041002
Permit Number 18041002
Review Stop P
Sequence Number 1
Notes
Date Text
2018-05-13 10:05:561) INDICATE ON THE SHT. 2 OF 3 IF THE EXISTING MAIN
 DRAIN IS GOING TO BE REPLACED OR REMAIN AS IS. THE MAIN
 DRAIN DETAILS SHOW A MAIN DRAIN TYPICAL OF 2 PLACES.
 WILL ONE BE A SUCTION FITTING ON THE WALL AND ONE ON
 THE POOL FLOOR OR WILL IT BE A DUAL OUTLET ON THE
 FLOOR? CLARIFY.
 2) THE PLANS ALSO NOTE A "VAC ALERT" AT THE PUMP.
 SUBMIT TWO COPIES OF MANUF. SPECS & INSTALLATION MANUAL
 FOR THE VAC ALERT SVRS UNIT. WPB AMEND. TO FBC SEC.
 107.2.1. UNIT SHALL COMPLY WITH APSP-7 SEC.7.1 &
 ANSI/ASME A112.19.17.
 3) REVISE THE PLAN NOTES IN THE BOX ABOVE THE POOL
 EQUIPMENT ANCHOR DETAIL TO REFER TO FBC SEC. 454
 INSTEAD OF 424.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  