| Plan Review Notes For Permit 18040983 |
| Permit Number |
18040983 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-05-03 13:13:25 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. IN THIS SUBMITTAL, THE ASSEMBLY WAS CHANGED TO AN | | | ASSEMBLY WITH A DP LIMITATION OF -75, WHICH DOES NOT | | | MEET THE REQUIREMENTS FOR ZONES 2 AND 3. SEE NOTE 9 ON | | | PAGE 2 OF 57, CALCULATIONS BY A QUALIFIED DESIGN | | | PROFESSIONAL REQUIRED. | | | | | | (PREVIOUS SUBMITTAL PROPOSED A SYSTEM WITH DP OF -157) |
|