| Plan Review Notes For Permit 18040945 |
| Permit Number |
18040945 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-13 11:12:35 | 1) PER APSP 7 -2013, THE MAXIMUM FLOW RATE FROM THE | | | MANUFACTURER'S PUMP CURVE CAN NO LONGER BE USED TO | | | DETERMINE MAXIMUM SYSTEM FLOW RATE. THE NEW CODE | | | SEPARATES METHODS FOR DETERMINING MAXIMUM SYSTEM FLOW | | | RATE INTO TWO CATEGORIES; UNSECURED SYSTEMS (TYPICAL | | | RESIDENTIAL SYSTEMS) AND SECURED SYSTEMS (TYPICAL | | | COMMERCIAL SYSTEMS). SUBMIT TOTAL TOTAL DYNAMIC HEAD | | | CALCULATIONS. | | | 2) SUBMIT TWO LEGIBLE COPIES OF THE POOL PUMP CURVE. | | | WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) IDENTIFY ON A LEGIBLE POOL PUMP CURVE THE SPECIFIC | | | PUMP THAT IS BEING INSTALLED. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 4) A GAS PERMIT APPLICATION HAS BEEN SUBMITTED IN THE | | | POOL PACKAGE BUT THERE ARE NO GAS PLANS. CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|