| Plan Review Notes For Permit 18040940 |
| Permit Number |
18040940 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-04-26 17:54:34 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #18040940 | | | 4/26/18 | | | | | | PLAN REVIEW | | | | | | 1) SHEET M0.3: PLEASE PROVIDE REVISED AC COOLING AND | | | HEATING CALCULATIONS FOR THE NEW LARGER TRANE RTU'S 6, | | | 7, 8, &10- SECTUION C403.2.1 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 2) M1.1: THE RETURN AIR TRANSFER FROM THE STORAGE ROOM | | | MAY BE PROHIBITED DEPENDING ON WHAT MATERIALS OR | | | EQUIPMENT ARE IN THE ROOM- SEE SECTION 918,6 (1, 2, & | | | 3), | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|