Plan Review Notes
Plan Review Notes For Permit 18040871
Permit Number 18040871
Review Stop M
Sequence Number 4
Notes
Date Text
2018-07-18 11:05:204TH REVIEW FBC-2014 MECHANICAL
 MASTER PERMIT #16110067
 REVISION PERMIT #18040871
 6/5//18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS IS THE 4TH REQUEST FOR COMPLETE ENGINEERING FOR
 INSTALLATION OF THE RTU'S AND DOAS-1. THE CORRECTED AND
 RESUBMITTED PLANS ARE PROVIDING ONLY THE UNIT
 ATTACHMENT TO THE CURBS BUT THE REMAINING DETAILS HAVE
 NOT BEEN PROVIDED. AS A RESULT, I HAVE CALLED THE MEP
 ENGINEER OF RECORD BRUCE CIARLARIELLO PE. WHO STATED
 THAT THE REMAINING DETAILS-
  
 ROOF OPENING FRAMING AND CURB TO ROOF STRUCTURE
 ATTACHMENT- ARE THE RESPONSIBILTY OF THE STRUCTURAL
 ENGINEER. PLEASE SEE COMMENT #1 FROM THE 1ST REVIEW
 DATED 4/27/18.
  
 2) PROVIDE COMPLETE ENGINEERED DETAILS FOR INSTALLATION
 OF THE NEW RTU'S INCLUDING THE NEW ROOF OPENINGS AND
 REINFORCEMENTS, CURB ATTACHMENTS TO THE STRUCTURE, AND
 UNIT ATTACHEMENTS TO THE CURBS- SECTION 301.15
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
 UPON RECEIPT OF THESE COMMENTS, PLEASE CONTACT ME AT
 YOUR EARLIEST CONVENIENCE.
  
 THANK YOU,
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  