Plan Review Notes
Plan Review Notes For Permit 18040871
Permit Number 18040871
Review Stop P
Sequence Number 3
Notes
Date Text
2018-06-25 13:42:001) MEANS FOR CONTROLLING EXPANSION SHALL BE PROVIDED BY
 AN EXPANSION TANK OR A THERMAL EXPANSION VALVE. ANY
 PRESSURE INCREASES DUE TO THERMAL EXPANSION OF THE
 WATER BEING HEATED MUST BE CONTROLLED TO PREVENT THE
 PRESSURE DOWNSTREAM OF A PRESSURE - REDUCING VALVE FROM
 BECOMING GREATER THAN THE SETTING OF THE VALVE.2014
 FBC-PLUMBING SEC.607.3 .
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW