Plan Review Notes
Plan Review Notes For Permit 18040871
Permit Number 18040871
Review Stop M
Sequence Number 3
Notes
Date Text
2018-06-21 15:13:483RD REVIEW FBC-2014 MECHANICAL
 MASTER PERMIT #16110067
 REVISION PERMIT #18040871
 6/5//18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M3.0: THE REQUESTED WIND LOAD ENGINEERING FOR
 THE RTU AND DOAS INSTALLATIONS IS INCOMPLETE. DETAILS
 LACKING: A) THE ROOF OPENING FRAMING AND
 REINFORCEMENTS. B) THE CURB ATTACHMENT TO THE ROOF
 STRUCTURE. C) THE LENGTH OF THE 1/2" ANCHOR BOLTS
 SPECIFIED TO ANCHOR THE DOAS TO THE CURB. D)
 MANUFACTURER'S SPECIFICATIONS FOR THE FACTORY CURBS.
  
 PLEASE NOTE THAT THE REMAINING ENGINEERING CAN BE A
 DEFERRED SUBMITTAL BY REQUEST.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  