Plan Review Notes
Plan Review Notes For Permit 18040871
Permit Number 18040871
Review Stop P
Sequence Number 2
Notes
Date Text
2018-06-03 03:53:201) SUBMIT THE ADDITIONAL SHEETS FOR THE MANUFACTURER'S
 SPECIFICATIONS FOR THE TANKLESS WATER HEATERS. THERE
 ARE A TOTAL OF 2 OR 3 SHHETS. THE SPECIFICATIONS MUST
 SHOW THE WATER HEATER IS LISTED AND LABELED PER THE
 2014 FBC-FUEL GAS SEC. 301.3.TWO COPIES OF THE
 SPECIFICATIONS ARE REQUIRED PER WPB AMEND. TO FBC SEC.
 107.2.1.
 2) MEANS SHALL BE PROVIDED FOR THERMAL EXPANSION FOR
 THE HOT WATER SYSTEM SINCE THESE TANKLESS WATER HEATERS
 ARE EQUIPPED WITH A BUFFER TANK AND A RECIRCULATION
 PUMP. 2014 FBC-PLUMBING SEC.607.3.
 3) THE ENTIRE RECIRCULATING LINE SHALL BE INSULATED
 WITH MINIMUM 1 INCH INSULATION INCLUDING THE FIRST 8
 FEET OF ALL BRANCH LINES PER 2014 FBC-PLUMBING SEC.
 607.5 , 2014 ENERGY CODE SEC. C404.5.
 4) SHT. P1.0 - SHOW THE LOCATION OF THE GAS METER ON
 THE PLAN. WPB AMEND. TO FBC SEC. 107.2.1.
 5) SHOW THE LOCATION OF THE MP REGULATOR FOR THE
 GENERATOR.WPB AMEND. TO FBC SEC. 107.2.1.
 6) SHOW THE SIZE OF THE HORIZONTAL GAS PIPNG TO THE
 DRYERS.
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. 411.1.3.2.THE CONNECTOR SHALL
 HAVE THE CAPACITY FOR THE TOTAL DEMAND OF THE CONNECTED
 APPLIANCE 2014 FBC-FUEL GAS SEC. 411.1.3.2.
 8) SHT. P4.2 - THE GAS SYSTEM SIZING AT THE METER IS
 STILL OVERSIZED. YOU SHOW THE SYSTEM AS BEING 2 PSI
 FROM THE GAS PURVEYOR ON SHT. P3.0 AND ALSO NOTE THIS
 ON SHT.P4.2. YOU SHOW AN MP REGULATOR ON THE GAS MAIN
 DOWNSSTREAM OF THE GAS METER AND SHUTOFF VALVE. WHAT IS
 THE PRESSURE ON THE SYSTEM DOWNSTREAM OF THIS
 REGULATOR? IF INDEED IT IS LESS THAN 2 PSI AT THIS
 POINT THEN ALL YOUR PE IS UNDERSIZED. THE PE PIPE WOULD
 HAVE TO BE OVER 4 INCHES IN DIAMETER TO HANDLE THE
 TOTAL BTU LOAD AT 250 FEET IN LENGTH. SECONDLY, IT IS
 NOT EVEN POSSIBLE TO SUPPLY A 2 INCH PE LINE FROM A 5
 INCH LINE AT THE SAME LOW PRESSURE.THE PLAN SHOWS MP
 REGULATORS SUPPLYING THE GAS EQUIPMENT/APPLIANCES. IF
 THE SYSTEM IS LESS THAN 2 PSI IN THE STRUCTURE, WHY THE
 NEED FOR THE REGULATORS? REMOVE THE REGULATOR
 DOWNSTREAM OF THE METER AND THE SIZE OF THE SCH. 40
 METALLIC PIPE FOR A 2 PSI SYSTEM DOWNSTREAM OF THE GAS
 METER CAN BE 2 INCH BASED ON 2014 FBC-FUEL GAS TABLE
 402.4 (5). AS DESIGNED, THE SYSTEM IS CONFUSING AND
 DOES NOT CCOMPLY WITH THE GAS CODE.
  
 NOTE: I SUGGEST CONTACTING THIS PLAN REVIEWER TO
 DISCUSS THE SIZING OF THE GAS SYSTEM.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  