Plan Review Notes
Plan Review Notes For Permit 18040871
Permit Number 18040871
Review Stop G
Sequence Number 2
Notes
Date Text
2018-06-25 13:48:231) INDICATE ON THE PLAN WHICH GAS SIZING TABLE IS BEING
 USED FOR THE SIZING OF THE LOW PRESSURE SYSTEM. THERE
 IS NO REFERENCE TO ANY TABLE. 2014 FBC-FUEL GAS
 SEC.402.3.
 2) THE SIZE OF THE HORIZONTAL GAS PIPING TO THE DRYERS
 MAY NOT BE ABLE TO BE 1/2" AS STATED IN THE PLAN REVIEW
 RESPONSE. THE SIZE WILL DEPEND ON THE SIZING TABLE
 BEING USED. THE PREVIOUS PLANS REFER TO TABLE 402.4 (1)
 FOR THE LOW PRESSURE SYSTEM AND THE 1/2 INCH LINE WILL
 NOT SUPPORT 495,000 BTU'S.
 3) MANUFACTURER'S INSTALLATION INSTRUCTIONS AND
 SPECIFICATIONS FOR THE REGULATORS, TANKLESS WATER
 HEATERS AND THE FLEX CONNECTOR FOR THE GENERATOR SHALL
 BE ONSITE FOR INSPECTION.
 4) SHT. P3.0 SHOWS THE GAS REGULATOR TO BE VENTED TO
 THE EXTERIOR AND SHT. P4.2 NOTES THE REGULATOR AS A
 NON-VENTING REGULATOR. WHICH IS IT? CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  