| Plan Review Notes For Permit 18040840 |
| Permit Number |
18040840 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-05-15 04:51:12 | 05/15/2018 PLUMBING 2ND REVIEW**DENIED** | | | | | | 1) THE 2017 5TH EDITION OF THE FBC PLUMBING 421.2 NOW | | | REQUIRES ALL WHIRLPOOL TUBS TO BE UL1795 LISTED, | | | PROVIDES DOCUMENTS TO SUPPORT THIS.2ND REQUEST. | | | | | | 2) THE THERMOSTATIC MIXING VALVE SUBMITTALS YOU HAVE | | | PROVIDED DOES NOT SHOW THE VALVE AS BEING NSF 61 | | | APPROVED. FBC-P 605.5. 2ND REQUEST. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | |
|