Plan Review Notes For Permit 18040840
Permit Number 18040840
Review Stop P
Sequence Number 1
Notes
Date Text
2018-04-19 18:34:1404/19/2018 PLUMBING 1ST REVIEW**DENIED**
  
 1) JOB VALUE SEEMS TOO LOW. PROVIDE BONA FIDE SIGNED
 CONTRACT. COST MUST INCLUDE ALL MATERIAL, LABOR,
 OVERHEAD, AND PROFIT. WPB AMEND TO THE FBC 109.3
  
 2) PROVIDE UP TO DATE PRODUCT APPROVALS AS THIS PLAN
 REVIEW HAS ATTEMPTED TO CONTACT HOME INNOVATION LABS
 AND THE PHONE LINE IS ALWAYS BUSY. APPROVALS SUBMITTED
 ARE 4 YEARS OLD AND NOT DATED BY PERSON CERTIFYING
 APPROVALS. FBC 107.3.5
  
 3) PROVIDE MANUFACTURES INSTALLATION MANUAL FOR TUB.
 FBC-P 421.2
  
 4) THE 2017 5TH EDITION OF THE FBC PLUMBING 421.2 NOW
 REQUIRES ALL WHIRLPOOL TUBS TO BE UL1795 LISTED,
 PROVIDES DOCUMENTS TO SUPPORT THIS.
  
 5) THE THERMOSTATIC MIXING VALVE SUBMITTALS YOU HAVE
 PROVIDED DOES NOT SHOW THE VALVE AS BEING NSF 61
 APPROVED. FBC-P 605.5
  
 6) PROVIDE LOCATION OF EXISTING TUB DRAIN ON FLOOR
 PLAN. FBC 107.3.5
  
 7) REMOVE COMMENT THAT NO TILE OR DRYWALL WORK TO BE
 DONE FROM PLAN AS YOU HAVE SUBMITTED DUROCK PRODUCT
 APPROVAL SHOWING THAT WORK WILL BE DONE. FBC 107.3.5
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  