| Date |
Text |
| 2018-10-17 15:57:58 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18040836 |
| | 10/17/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REFER TO SECTION 306.5 AND PROVIDE AN INTERIOR OR |
| | EXTERIOR MEANS OF ACCESS TO THE ROOFTOP MECHANICAL |
| | EQUIPMENT. PLEASE NOTE THAT ACCESS SHALL NOT REQUIRE |
| | THE USE OF PORTABLE LADDERS. |
| | |
| | 2) SHEET M-1: THE PLAN INDICATES "CONTINUOUS" EXHAUST |
| | VENTILATION TO BE CONTROLLED BY A SWITCH, HOWEVER THE |
| | DEFINITION OF CONTINUOUS INDICATES THE FUNCTION TO BE |
| | UNINTERRUPTED. PLEASE PROVIDE A VENTILATION SYSTEM THAT |
| | IS IN COMPLIANCE. |
| | |
| | 3) REFER TO PAGE 2 OF THE MITSUBISHI CONDENSER |
| | INSTALLATION SUBMITTAL. THE DETAIL INDICATES THAT THE |
| | ROOF STAND IS TO BE PROVIDED "BY OTHERS". PLEASE SUBMIT |
| | A VALID FL. PRODUCT APPROVAL OR A MIAMI-DADE NOA FOR |
| | THE STAND. |
| | |
| | 4) THE REQUESTED ENGINEERING FOR INSTALLATION OF THE |
| | ROOFTOP EXHAUST FAN WAS NOT PROVIDED- SECTION 107.2.1 |
| | WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |