| 2018-08-20 15:48:47 | 2ND REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS |
| | |
| | 3. SHT. P-1 REFERENCES THE CIVIL DRAWING FOR THE |
| | LOCATION AND SIZE OF THE GREASE INTERCEPTOR NO CIVIL |
| | DRAWING WAS INCLUDED IN THIS PLAN SET. PLEASE PROVIDE |
| | CIVIL DRAWING SHOWING SIZE AND LOCATION OF THE GREASE |
| | INTERCEPTOR ,. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. PROVIDE SIZING CALCULATIONS FOR THE GREASE |
| | INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | I COULD NOT LOCATE A CIVIL DRAWING WITH THE ABOVE |
| | INFORMATION PLEASE INCLUDE IN NEXT SUBMITTAL PLAN PAGE. |
| | |
| | NEW COMMENT: |
| | 1. PROVIDE PIPING DETAIL FOR GREASE INTERCEPTOR |
| | INCLUDING CLEANOUTS AND TEST PORT ON OUTLET OF TANK. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. SHT. A100 SHOWS THE ROOF BEING PITCHED TOWARD TWO |
| | DIFFERENT MAIN ROOF SCUPPER DRAINS. ARE THESE COMBINED |
| | PRIMARY AND SECONDARY ROOF DRAINS PLEASE SHOW LOCATION |
| | OF THE EMERGENCY / SECONDARY DRAINS OR SHOW COMPLIANCE |
| | WITHE THE FOLLOWING CODE SECTION. FBC PL 1108.1 |
| | SECONDARY (EMERGENCY OVERFLOW) DRAINS OR SCUPPERS. |
| | WHERE ROOF DRAINS ARE REQUIRED, SECONDARY (EMERGENCY |
| | OVERFLOW) ROOF DRAINS OR SCUPPERS SHALL BE PROVIDED |
| | WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS ABOVE THE |
| | ROOF IN SUCH A MANNER THAT WATER WILL BE ENTRAPPED IF |
| | THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY REASON. WHERE |
| | PRIMARY AND SECONDARY ROOF DRAINS ARE MANUFACTURED AS A |
| | SINGLE ASSEMBLY, THE INLET AND OUTLET FOR EACH DRAIN |
| | SHALL BE INDEPENDENT. |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |