| 2018-05-26 08:26:35 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE OUTLET OF THE TOILET PAPER DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR. PER FBC ACC 604.7 |
| | |
| | 2. PLEASE PROVIDE A DETAIL FOR THE EMERGENCY SCUPPER |
| | AND SHOW COMPLIANCE WITH FBC 1503.4.2.1 OVERFLOW |
| | SCUPPERS. WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW |
| | WATER IS NOT PROVIDED, OVERFLOW SCUPPERS SHALL BE |
| | PLACED IN WALLS OR PARAPETS NOT LESS THAN 2 INCHES NOR |
| | MORE THAN 4 INCHES ABOVE THE FINISHED ROOF COVERING AND |
| | SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED |
| | VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET |
| | SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. |
| | |
| | 3. SHT. P-1 REFERENCES THE CIVIL DRAWING FOR THE |
| | LOCATION AND SIZE OF THE GREASE INTERCEPTOR NO CIVIL |
| | DRAWING WAS INCLUDED IN THIS PLAN SET. PLEASE PROVIDE |
| | CIVIL DRAWING SHOWING SIZE AND LOCATION OF THE GREASE |
| | INTERCEPTOR , WATER METER AND BACKFLOW. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | 4. PROVIDE SIZING CALCULATIONS FOR THE GREASE |
| | INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. PLACE NOT ON PLAN TEMPERED WATER SHALL BE DELIVERED |
| | FROM LAVATORIES AND GROUP WASH FIXTURES LOCATED IN |
| | PUBLIC TOILET FACILITIES PROVIDED FOR CUSTOMERS, |
| | PATRONS AND VISITORS. TEMPERED WATER SHALL BE DELIVERED |
| | THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE |
| | THAT CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL |
| | 416.5 |
| | |
| | 6. THE FLOOR SINK SHALL BE EQUIPPED WITH A TRAP PRIMER |
| | VALVE. PER FBC PL 1002.4.1 |
| | |
| | 7. WHAT IS THE FLOOR SINK BEING USED TO DRAIN PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. WHAT IS THIS SPACE GOING TO BE USED FOR IS THERE |
| | GOING TO BE COOKING OR FOOD PREP ON PROPERTY OR WILL IT |
| | BE USED TO STORE COOKING EQUIPMENT WITH ANY KIND OF |
| | FLAMMABLE GASES, LIQUIDS OR SOLID FUEL PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. ON THE COVER SHEET THE CODE REVIEW LIST THE 2014 |
| | PLUMBING AND ACCESSIBILITY THIS PROJECT SHALL COMPLY |
| | WITH FBC PLUMBING AND ACCESSIBILITY 2017 6TH EDITION. |
| | PLEAS CLARIFY PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |