| 2018-05-21 17:44:04 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18040836 |
| | 5/21/18 |
| | |
| | CODES IN EFFECT: |
| | FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) SHEETS A300 & M-1: THE OUTSIDE INTAKE APPEARS TO BE |
| | WITHIN THE 10' MINIMUM REQUIRED CLEARANCE TO THE |
| | DRIVEWAY- SEE SECTION 401.4(2) FBC MC. |
| | |
| | 2) M-100: PROVIDE A FLORIDA PRODUCT APPROVAL OR |
| | MIAMI-DADE NOA FOR THE LOUVER PER FAC RULE 9N-3. SUBMIT |
| | SPECS FOR THE LOUVER SHOWING COMPLIANCE WITH 401.5 FBC |
| | MC. |
| | |
| | 3) M-300: PROVIDE THE WIND LOAD DESGIN CRITERIA FOR TIE |
| | DOWN OF THE RTU AND CURB- SEE SECTION 1609 FBC BC. |
| | |
| | 4) M-300: CURB BOLT INFORMATION NOT PROVIDED ON |
| | MECHANICAL OR STRUCTURAL PLANS. PROVIDE THE TYPE AND |
| | SIZE OF BOLT, DEPTH OF EMBEDMENT, AND SPACING OF BOLTS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |