| Plan Review Notes For Permit 18040814 |
| Permit Number |
18040814 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-05-24 12:21:20 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. FROM FIRST REVIEW: THE PLANS PROVIDED ARE NOT SIGNED | | | AND SEALED AND LACK THE TITLE BLOCK FOR THE ENGINEER | | | WHO WILL TAKE RESPONSIBILITY, FS 471. THE CALCULATIONS | | | APPEAR TO INCLUDE THE SAME INFORMATION, BUT IS TOO | | | SMALL TO READ. | | | | | | PROVIDE SIGNED AND SEALED FULL SIZE DRAWINGS, FBC 107. | | | | | | 2ND REVIEW - THE PLAN SIZE PAGES WERE NOW SUBMITTED | | | REDUCED (11X17), LIGHT PLANS SUBMITTED. PLANS ARE | | | DIFFICULT TO READ AS THEY ARE LIGHT AND REDUCED. | | | PROVIDE EASILY READIBLE PLANS. PLANS ARE TO BE OF | | | SUFFICIENT QUALITY TO BE REVIEWED, SCANNED, AND USED | | | FOR INSPECTIONS IN THE FIELD. | | | | | | 2. DELEGATED ENGINEERING IS TO BE REVIEWED BY | | | STRUCTURAL ENGINEER OF RECORD, FAC61G15. | | | |
|