| 2018-07-14 13:06:50 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. REVISE PLAN TO INCLUDE THE FOLLOWING INFORMATION: |
| | |
| | FBC B 705.3, BUILDINGS ON THE SAME LOT, SHOW DISTANCE |
| | FROM PROPOSED SHED TO ASSUMED PROPERTY LINE (DISTANCE |
| | FROM EX. RESIDENCE #325 TO ASSUMED PROPERTY LINE, |
| | DISTANCE FROM PROPOSED STORAGE SHED TO ASSUMED PROPERTY |
| | LINE, SHOW COMPLIANCE FOR BOTH STRUCTURES) |
| | |
| | PLAN SHOWS 6' BUT DOES NOT INCLUDE INFORMATION |
| | REGARDING DISTANCE FROM EX. RESIDENCE #325 TO ASSUMED |
| | PROPERTY LINE. |
| | |
| | SINCE THE PROPOSED STRUCTURE DOES NOT APPEAR TO HAVE |
| | ANY OPENINGS ON THE SIDE FACING THE EXISTING STRUCTURE, |
| | IT IS SUGGESTED THAT THE ASSUMED PROPERTY LINE BE |
| | PLACED AT THE STRUCTURE TO GIVE MORE FLEXIBILITY FOR |
| | SHOWING COMPLIANCE FOR THE EXISTING WOOD STRUCTURE (IF |
| | PROPOSED CONSTRUCTION MEETS 2 HOUR REQUIREMENT). FOR |
| | INSTANCE, SEE FBC B TABLE 705.8, TABLE 602. |
| | |
| | NOTE THAT BUILDING TYPE CAN BE DECLARED AS THE MINIMUM |
| | REQUIRED BY CODE RATHER THAN ACTUAL CONSTRUCTION TYPE. |
| | |
| | SEE ALSO FBC B 705.3 EXCEPTION 1. |
| | |
| | PLEASE REVISE PLAN TO SHOW ANY FIRE RATINGS REQUIRED. |
| | |
| | PLEASE CONTACT ME IF YOU WISH TO DISCUSS. |
| | |
| | |