| Plan Review Notes For Permit 18040798 |
| Permit Number |
18040798 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-22 07:14:49 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. REVISE PLAN TO INCLUDE THE FOLLOWING INFORMATION: | | | | | | FBC B TABLE 504.4, TABLE 506.2 (BUILDING HEIGHT AND | | | AREA) | | | FBC B CHAPTER 6, BUILDING TYPE | | | FBC B TABLE 602, FIRE RESISTANCE RATING REQUIREMENTS | | | FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCE | | | FBC B 705.3, BUILDINGS ON THE SAME LOT, SHOW DISTANCE | | | FROM PROPOSED SHED TO ASSUMED PROPERTY LINE (DISTANCE | | | FROM EX. RESIDENCE #325 TO ASSUMED PROPERTY LINE, | | | DISTANCE FROM PROPOSED STORAGE SHED TO ASSUMED PROPERTY | | | LINE, SHOW COMPLIANCE FOR BOTH STRUCTURES) | | | FBC B 1603.1.4, WIND DESIGN CRITERIA | | | FBC 107, GOVERNING CODE | | | |
|