| 2018-06-29 15:35:33 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PROVIDE GRAPH/CALCULATION OF EXTERIOR LIGHTING POWER |
| | ALLOWANCES PER THE FBC ENERGY CONSERVATION IN RELATION |
| | TO THE CONNECTED EXTERIOR LIGHTING PROPOSED TO COMPLY |
| | WITH CODE. FBC EC C405.5.1 (COMMENT RESPONSE STATES |
| | THAT THIS CODE REFERS TO INTERIOR LIGHTING. I'M NOT |
| | SURE WHICH YEAR CODE YOU ARE LOOKING AT, BUT IN THE |
| | 2017 FBC ENERGY CONSERVATION, THIS SECTION IS FOR |
| | EXTERIOR LIGHTING. IT APPEARS THAT YOU ARE REQUESTING |
| | EXEMPTION THAT IS USED FOR THEME ELEMENTS IN |
| | AMUSEMENT/THEME PARKS, WHICH DOES NOT APPLY TO THIS |
| | SUBMITTAL. PROVIDE AS PREVIOUSLY REQUESTED. YOU ARE |
| | WELCOME TO DISCUSS THIS WITH THE BUILDING OFFICIAL IF |
| | YOU DISAGREE.) |
| | 2. WILL CAMERAS HAVE HIGH VOLTAGE WIRING IN ADDITION TO |
| | LOW VOLTAGE WIRING? PROVIDE CLARIFICATION. FBC 107.2.1 |
| | (BASED ON COMMENT RESPONSE, PROVIDE DETAIL OF |
| | SEPARATION FOR LOW VOLTAGE WIRING FROM POWER WIRING. |
| | NEC 725.136) |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |