Plan Review Notes
Plan Review Notes For Permit 18040791
Permit Number 18040791
Review Stop E
Sequence Number 3
Notes
Date Text
2018-11-29 15:17:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. GUEST HOUSE DOES NOT HAVE 2 SMALL APPLIANCE BRANCH
 CIRCUITS. 210.52B1 NEC (THIS ITEM HAS NOT BEEN
 ADDRESSED. PROVIDE CORRECTION AS PREVIOUSLY NOTED.)
  
 2. CORRECTED.
  
 3. CORRECTED.
  
 4. SMOKE DETECTORS MUST BE MINIMUM 3FT AWAY FROM
 BATHROOM DOORS. NFPA 72 29.8.3.4 #6 (THIS HAS NOT BEEN
 CORRECTED ON PLAN. BOTH BEDROOM SMOKE ALARMS ARE WITHIN
 3 FEET OF BATHROOM DOOR. PROVIDE CORRECTION AS
 PREVIOUSLY NOTED. FBC RE 314.3 #4)
  
 5. PROVIDE ACCURATE LOAD CALCULATION. NEC 220; FBC RE
 R3602.1 (LOAD CALCULATION PROVIDED IS NOT ACCURATE. SEE
 FORMAT PROVIDED IN THE FBC RESIDENTIAL. A LOAD
 CALCULATION SHOULD BE PROVIDED FOR THE MAIN SERVICE
 WHICH INCLUDES ALL LOADS, AND FOR THE SUB-PANEL TO THE
 GUEST HOUSE. CURRENTLY, THE GUEST HOUSE PANEL IS SHOWN
 AS A 100 AMP RATED PANEL IN THE PANEL SCHEDULE.THIS
 PANEL WOULD BE OVERLOADED BASED ON THE LOAD
 DESCRIPTIONS PROVIDED WITH THE ADDITIONAL LOADS
 REQUIRED THAT ARE NOT SHOWN. PROVIDE CORRECTION. NEC
 220, 408.30; FBC RE E3602.3
  
 6. COMBINED LOAD CALCS (WHICH AREN'T ACCURATE BECAUSE
 OF THE MISSING SMALL APPLIANCE CIRCUITS) EQUAL TO
 GREATER THAN A 200AMP SERVICE. TOTAL WAS 214AMPS.
 230.42 AND 220.40NEC (LOAD CALCULATION NOT CORRECT, SEE
 NOTE 5, MAKE SURE TO INCLUDE 1500 VA FOR EACH SMALL
 APPLIANCE CIRCUIT.)
  
 NEW COMMENT:
  
 7. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE NEXT
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN
 REVIEW IS REQUIRED. FLORIDA STATUTES STATE: WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FOR THIS
 PARTICULAR PLAN, THE ADDITIONAL FEE WOULD BE $2,274.00
 FS 553.80(2)(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  
  