Plan Review Notes
Plan Review Notes For Permit 18040791
Permit Number 18040791
Review Stop P
Sequence Number 2
Notes
Date Text
2018-09-13 12:19:372ND REVIEW: FBC 2017 6TH EDITION
 PERMIT 18040791
 PLUMBING COMMENTS: DENIED
  
 1. TANKLESS WATER HEATER: ECO-11 TANKLESS WATER HEATER
 LISTED ON ELECTRICAL SCHEDULE IS DESIGNATED BY THE
 MANUFACTURER AS A POINT OF USE UNIT DESIGNED FOR USE
 WITH SINGLE FIXTURE. PROVIDE WATER HEATER DESIGNED FOR
 WHOLE HOUSE USE OR PROVIDE ONE EACH DESIGNATED ECO-11
 FOR EACH FIXTURE, INSTALLING ADJACENT TO FIXTURE AND
 SHOWN ON THE PLAN AS SUCH. FPC RES P2801.1
 2. TANKLESS WATER HEATER: REGARDING THE INSTALLATION OF
 THE WATER HEATER IN THE ATTIC, PROVIDE NOTE THAT ATTIC
 SPACE SHALL BE PROVIDED TO COMPLY WITH THE REQUIREMENTS
 OF FBC RES M1305.1.3 AS DIRECTED BY FBC RES P2108.4 AND
 M2005.1
 A. INCLUDED HERE FOR YOUR USE IS THE EXCERPT
 M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 20 FEET (6096 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE NOT LESS THAN 30 INCHES (762 MM) DEEP AND 30
 INCHES (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES
 OF THE APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR
 ACCESS OPENING DIMENSIONS SHALL BE NOT LESS THAN OF 20
 INCHES BY 30 INCHES (508 MM BY 762 MM), AND LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE.
 3. RE: PLUMBING SPECIFICATION; NOTE 7: DELETE VERBAGE
 "AS SELECT BY OWNER" AND REPLACE WITH MANUFACTURER"S
 SPECIFICATIONS, TO INCLUDE BRAND NAME, MODEL NUMBER,
 ELECTRICAL CHARACTERISTICS, COMPONENTS, DEVICES,
 FIXTURES, AND EQUIPMENT SHALL BE LISTED FOR THE
 APPLICATION, SHALL BEAR THE LABEL OF AN APPROVED AGENCY
 AND SHALL BE INSTALLED, AND USED, OR BOTH, IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS. 2017 FBC R 2801.3 INSTALLATION
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715