| 2018-09-13 12:19:37 | 2ND REVIEW: FBC 2017 6TH EDITION |
| | PERMIT 18040791 |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. TANKLESS WATER HEATER: ECO-11 TANKLESS WATER HEATER |
| | LISTED ON ELECTRICAL SCHEDULE IS DESIGNATED BY THE |
| | MANUFACTURER AS A POINT OF USE UNIT DESIGNED FOR USE |
| | WITH SINGLE FIXTURE. PROVIDE WATER HEATER DESIGNED FOR |
| | WHOLE HOUSE USE OR PROVIDE ONE EACH DESIGNATED ECO-11 |
| | FOR EACH FIXTURE, INSTALLING ADJACENT TO FIXTURE AND |
| | SHOWN ON THE PLAN AS SUCH. FPC RES P2801.1 |
| | 2. TANKLESS WATER HEATER: REGARDING THE INSTALLATION OF |
| | THE WATER HEATER IN THE ATTIC, PROVIDE NOTE THAT ATTIC |
| | SPACE SHALL BE PROVIDED TO COMPLY WITH THE REQUIREMENTS |
| | OF FBC RES M1305.1.3 AS DIRECTED BY FBC RES P2108.4 AND |
| | M2005.1 |
| | A. INCLUDED HERE FOR YOUR USE IS THE EXCERPT |
| | M1305.1.3 APPLIANCES IN ATTICS. |
| | ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN |
| | OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE |
| | ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT |
| | NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES |
| | (559 MM) WIDE AND NOT MORE THAN 20 FEET (6096 MM) LONG |
| | MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM |
| | THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE |
| | CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5 |
| | NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE |
| | SPACE NOT LESS THAN 30 INCHES (762 MM) DEEP AND 30 |
| | INCHES (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES |
| | OF THE APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR |
| | ACCESS OPENING DIMENSIONS SHALL BE NOT LESS THAN OF 20 |
| | INCHES BY 30 INCHES (508 MM BY 762 MM), AND LARGE |
| | ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE. |
| | 3. RE: PLUMBING SPECIFICATION; NOTE 7: DELETE VERBAGE |
| | "AS SELECT BY OWNER" AND REPLACE WITH MANUFACTURER"S |
| | SPECIFICATIONS, TO INCLUDE BRAND NAME, MODEL NUMBER, |
| | ELECTRICAL CHARACTERISTICS, COMPONENTS, DEVICES, |
| | FIXTURES, AND EQUIPMENT SHALL BE LISTED FOR THE |
| | APPLICATION, SHALL BEAR THE LABEL OF AN APPROVED AGENCY |
| | AND SHALL BE INSTALLED, AND USED, OR BOTH, IN |
| | ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION |
| | INSTRUCTIONS. 2017 FBC R 2801.3 INSTALLATION |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |