| 2018-08-29 17:05:53 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. GUEST HOUSE DOES NOT HAVE 2 SMALL APPLIANCE BRANCH |
| | CIRCUITS. 210.52B1 NEC |
| | |
| | 2. GUEST HOUSE HAS NO LIGHT AND SWITCH FOR ATTIC BY |
| | ATTIC ACCESS. 210.70A3 NEC |
| | |
| | 3. TANKLESS WATER HEATER IN ATTIC HAS NO DISCONNECT |
| | 422.30 NEC |
| | |
| | 4. SMOKE DETECTORS MUST BE MINIMUM 3FT AWAY FROM |
| | BATHROOM DOORS. NFPA 72 29.8.3.4 #6 |
| | |
| | 5. CANNOT USE OPTIONAL LOAD CALC FROM 220.82, THAT IS |
| | FOR A SINGLE DWELLING UNIT ONLY |
| | |
| | 6. COMBINED LOAD CALCS (WHICH AREN'T ACCURATE BECAUSE |
| | OF THE MISSING SMALL APPLIANCE CIRCUITS) EQUAL TO |
| | GREATER THAN A 200AMP SERVICE. TOTAL WAS 214AMPS. |
| | 230.42 AND 220.40NEC |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |