| 2018-05-18 08:18:14 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. A MINIMUM OF TWO SMALL APPLIANCE BRANCH CIRCUITS |
| | MUST BE INCLUDED IN THE LOAD CALCULATION. PROVIDE |
| | CORRECTION. NEC 220; FBC RE E3602.2 |
| | 2. PLAN SHOWS A TANKLESS WATER HEATER IN ATTIC, BUT |
| | PANEL SCHEDULE INCLUDES THE LOAD FOR A NORMAL WATER |
| | HEATER. PROVIDE SPEC SHEET FOR TANKLESS TO CONFIRM |
| | LOAD. ADJUST LOAD CALCULATION IF NECESSARY. NEC 110.3, |
| | NEC 220; FBC RE E3602.2 |
| | 3. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| | FBC EC C405.1, R404.1 |
| | 4. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A |
| | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH |
| | CIRCUIT. NEC 250.32; FBC RE3607.3 |
| | 5. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| | MAIN BREAKER AT THE PANEL FOR SUB-PANEL. NEC 225.31, |
| | 225.32 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |