| Notes |
| Date |
Text |
| 2018-04-23 11:18:57 | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | ONLY ONE SET OF PLANS AND SPECS SUBMITTED, ALSO PLANS | | | NEED TO BE 1/8" SCALE MINIMUM. TO SMALL TO READ | | | | | | NEED A SHEET SHOWING THE SIGNS THAT ARE TO BE APPLIED | | | TO THIS SYSTEM AND WHERE THEY GO.690.7, 690.7, 690.10, | | | 690.13(B), 690.17(E) 690.31(G)(3), 690.31(G)(4), | | | 690.35(F), 690.56(B), 690.56(C) | | | | | | PLANS SHOW INVERTER FEEDING TWO SEPARATE PANELS, PLEASE | | | EXPLAIN WHAT SMALL SECOND PANEL IS FOR AND IF IT IS | | | EXISTING. HOW DOES THIS WORK? TWO LOADS? | | | | | | NEED TO EXPLAIN HOW BATTERY SYSTEM WILL WORK AND WHAT | | | THE PURPOSE OF BATTERY SYSTEM. DOES IT HAVE AN OUTSIDE | | | BRANCH CIRCUIT FEEDING IT TO CHARGE IT? | | | IF USED FOR STORAGE SEE 690.71 | | | | | | WHAT IS THE FUNCTION OF THE AUTO TRANSFROMER. | | | | | | PLEASE SUBMIT A SIGNED CONTRACTO FOR THE WORK INVOLVED. | | | $3.50 PER WATT IS WHAT WE USE FOR SYSTEMS WITHOUT | | | BATTERY BACKUP OR STORAGE? | | | | | | NEED TO SHOW ACCESS PATHWAYS ON ROOF ON PLAN FIRE CODE | | | 11.12.2.2.2..1 | | | | | | MAIN TO BE GROUPED 690.13(E) CAN NOT TELL FROM DRAWING | | | IF LOAD SIDE MAINS OF INVERTER ARE GROUPED. |
|