Plan Review Notes
Plan Review Notes For Permit 18040726
Permit Number 18040726
Review Stop E
Sequence Number 1
Notes
Date Text
2018-04-23 11:18:57 
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 ONLY ONE SET OF PLANS AND SPECS SUBMITTED, ALSO PLANS
 NEED TO BE 1/8" SCALE MINIMUM. TO SMALL TO READ
  
 NEED A SHEET SHOWING THE SIGNS THAT ARE TO BE APPLIED
 TO THIS SYSTEM AND WHERE THEY GO.690.7, 690.7, 690.10,
 690.13(B), 690.17(E) 690.31(G)(3), 690.31(G)(4),
 690.35(F), 690.56(B), 690.56(C)
  
 PLANS SHOW INVERTER FEEDING TWO SEPARATE PANELS, PLEASE
 EXPLAIN WHAT SMALL SECOND PANEL IS FOR AND IF IT IS
 EXISTING. HOW DOES THIS WORK? TWO LOADS?
  
 NEED TO EXPLAIN HOW BATTERY SYSTEM WILL WORK AND WHAT
 THE PURPOSE OF BATTERY SYSTEM. DOES IT HAVE AN OUTSIDE
 BRANCH CIRCUIT FEEDING IT TO CHARGE IT?
 IF USED FOR STORAGE SEE 690.71
  
 WHAT IS THE FUNCTION OF THE AUTO TRANSFROMER.
  
 PLEASE SUBMIT A SIGNED CONTRACTO FOR THE WORK INVOLVED.
 $3.50 PER WATT IS WHAT WE USE FOR SYSTEMS WITHOUT
 BATTERY BACKUP OR STORAGE?
  
 NEED TO SHOW ACCESS PATHWAYS ON ROOF ON PLAN FIRE CODE
 11.12.2.2.2..1
  
 MAIN TO BE GROUPED 690.13(E) CAN NOT TELL FROM DRAWING
 IF LOAD SIDE MAINS OF INVERTER ARE GROUPED.